# Project Tracker ID Source Status Priority Standard(s) Subject Updated
540 IEC 61850 User Feedback Task Force Feature 21 IOP_2017/35 Closed Normal

IEC 61850-6

Some SCT tools are removing incomplete Inputs with ExtRef’s of serviceType=”SMV” that are used for late binding of sample values 06/21/2022 09:24 AM Actions
506 IEC 61850 User Feedback Task Force Support 21 IOP_2015 Closed Normal

6

Issue 1: Content of CID with GOOSE Subscriptions During testing we noticed some CID files contained a single IED, whereas others 06/21/2022 09:12 AM Actions
464 IEC 61850 User Feedback Task Force Support 21 IOP_2013 Closed Normal There is an issue about differentiation between “fixed” /preconfigured DataSets and those that can be changed in a SCT. Some ICT 06/21/2022 09:00 AM Actions
430 IEC 61850 User Feedback Task Force Support 21 ENTSO-E Closed Normal IED certification needs to include tool interoprability validation 02/11/2021 07:36 AM Actions
539 IEC 61850 User Feedback Task Force Support 20 IOP_2017/34 Closed Normal

IEC 61850-6

Relation between GCB instances in scd to the related LGOS 06/21/2022 09:24 AM Actions
505 IEC 61850 User Feedback Task Force Support 20 IOP_2015 Closed Normal

6

Statement: an SCT A export an SED file with engineering rights “fix” and expectation was SCT B could add Goose clients after imp 06/21/2022 09:12 AM Actions
429 IEC 61850 User Feedback Task Force Support 20 ENTSO-E Closed Normal

IEC 61850-6/7-1

Input configuration: IEDs shall support ExtRef entries pointing to Data Objects as well as to DataAttribute with all possible le 02/11/2021 07:37 AM Actions
463 IEC 61850 User Feedback Task Force Feature 20 IOP_2013 Closed High

IEC 61850-6

GOOSE suscription: managing data types in datasets 02/11/2021 05:56 AM Actions
406 IEC 61850 User Feedback Task Force Bug 2.3 ENTSO-E Closed High Configuration of datasets by users 02/03/2021 03:55 PM Actions
405 IEC 61850 User Feedback Task Force Feature 2.2 ENTSO-E Closed Normal Optionality of DO/DA from the point of view of users 02/11/2021 06:20 AM Actions
404 IEC 61850 User Feedback Task Force Feature 2.1 ENTSO-E Closed Normal Meaning of "optional" regarding data model 02/11/2021 06:21 AM Actions
521 IEC 61850 User Feedback Task Force Feature 2 IOP_2017/3 Closed Normal

IEC 61850-8-1

The GSEControl has a datSet element indicating that the gocb is configured (but with no communication entry) 06/21/2022 09:24 AM Actions
487 IEC 61850 User Feedback Task Force Support 2 IOP_2015 Closed Normal

6

In the service section, there is the new element “client services”. That element includes GOOSE (default FALSE). Is it required 06/21/2022 09:11 AM Actions
445 IEC 61850 User Feedback Task Force Bug 2 IOP_2013 Closed High

IEC 61850-6

ExtRef use for GOOSE and SV subscription 02/11/2021 06:32 AM Actions
600 IEC 61850 User Feedback Task Force Feature 1947 IOP_2019 Closed Normal

IEC 61850-7-1

Connect the ExtRef - different supported mechanisms by ICT 06/21/2022 09:29 AM Actions
538 IEC 61850 User Feedback Task Force Support 19 IOP_2017/29 Closed Normal

IEC 61850-6

SCT engineering problems 06/21/2022 09:24 AM Actions
504 IEC 61850 User Feedback Task Force Support 19 IOP_2015 Closed Normal

6

When IID file from ICT includes “mustUnderstand” attribute in <GSEcontrol> such as <GSEControl desc="System Logical Device GOOS 06/21/2022 09:12 AM Actions
462 IEC 61850 User Feedback Task Force Support 19 IOP_2013 Closed Normal The use of ExtRef to subscribe to a SV was questioned. There are several different mechanisms that could be used in 61850-6 to s 06/21/2022 09:00 AM Actions
428 IEC 61850 User Feedback Task Force Support 19 ENTSO-E Closed Normal

IEC 61850-6

If 11 # ENTSO-E is not supported, vendors shall describe in the PIXIT document what they support 02/11/2021 07:40 AM Actions
591 IEC 61850 User Feedback Task Force Feature 1857 IOP_2019 Closed Normal

IEC 61850-6

A reservation could not be made via SCL for an IED’s report due to the lack of a ConnectedAP associated with the client’s AP 07/05/2022 08:34 AM Actions
537 IEC 61850 User Feedback Task Force Support 18 IOP_2017/27 Closed Normal

IEC 61850-7-2, 8-1, 8-2

Server is not responding to some of the MMS requests. (see below) What should the client do this case? 06/21/2022 09:24 AM Actions
503 IEC 61850 User Feedback Task Force Support 18 IOP_2015 Closed Normal

6

Issue 1: History section is present in ICD but during import SCT is discarding this history section. Also, maintenance of histor 06/21/2022 09:12 AM Actions
427 IEC 61850 User Feedback Task Force Support 18 ENTSO-E Closed Normal Functional constrained data shall include all levels of a hierarchy 02/11/2021 07:41 AM Actions
461 IEC 61850 User Feedback Task Force Improvement 18 IOP_2013 Closed High

IEC 61850-6

GOOSE Suscription definition in SCL 02/11/2021 06:03 AM Actions
596 IEC 61850 User Feedback Task Force Feature 1710 IOP_2019 Closed Normal An IED declares constraints that are not machine processable 02/11/2021 06:43 AM Actions
589 IEC 61850 User Feedback Task Force Feature 1700 IOP_2019 Closed Normal

IEC 61850-6

Usage of max of RptEnabled when indexed attribute is false and the relationship to RptEnabled 07/05/2022 08:28 AM Actions
536 IEC 61850 User Feedback Task Force Support 17 IOP_2017/26 Closed Normal SCT did not import GOOSE and 3 of the sampled value control blocks that existed in PMU ICD file. This caused validation failures 06/21/2022 09:13 AM Actions
502 IEC 61850 User Feedback Task Force Support 17 IOP_2015 Closed Normal

6

Issue 1: During import of SSD file SST/SCT is not able to recognize Busbar connection node. It is connectivity node and there i 06/21/2022 09:12 AM Actions
460 IEC 61850 User Feedback Task Force Support 17 IOP_2013 Closed Normal The usage of ClientLN in RptEna is optional. What does this mean. 61850-6 made this option for backward compatibility with ED.1. 06/21/2022 09:00 AM Actions
426 IEC 61850 User Feedback Task Force Support 17 ENTSO-E Closed Normal

IEC 61850-6

SCT and ICD Service section handling 02/11/2021 07:43 AM Actions
595 IEC 61850 User Feedback Task Force Feature 1642_04 IOP_2019 Closed Normal

IEC 61850-7-1

How does the SCT know whether to configure the LSVS.SvCBRef (if it is not configured)? 06/21/2022 09:29 AM Actions
594 IEC 61850 User Feedback Task Force Feature 1642_01 IOP_2019 Closed Normal

IEC 61850-6

Reverse engineering of subscription is not possible when Server and ServerAt APs are connected to the same SubNetwork 06/21/2022 09:29 AM Actions
593 IEC 61850 User Feedback Task Force Feature 1601 IOP_2019 Closed Normal

IEC 61850-6

How to disable SV control blocks that are not in use? 06/21/2022 09:29 AM Actions
535 IEC 61850 User Feedback Task Force Support 16 IOP_2017/25 Closed Normal

6

SCD file removed unconfigured GOOSE control block but did not remove the Connected AP section contained GSE information. 06/21/2022 09:13 AM Actions
501 IEC 61850 User Feedback Task Force Support 16 IOP_2015 Closed Normal

6

PAUL MYRDA: In SCL it is possible to define unbuffered report control blocks with indexed set to false but with max instances se 06/21/2022 09:12 AM Actions
425 IEC 61850 User Feedback Task Force Support 16 ENTSO-E Closed Normal

IEC 61850-6

Restrictions in the configuration to be described in the ICD Service section 02/11/2021 07:44 AM Actions
459 IEC 61850 User Feedback Task Force Bug 16 IOP_2013 Closed High

IEC 61850-6

No mechanism in SCL to indicate if the SCT can define/delete/edit RCBs/ExtRefs 06/21/2022 09:00 AM Actions
588 IEC 61850 User Feedback Task Force Feature 1548 IOP_2019 Closed Normal

IEC 61850-6

More than one redundant PhysConn for ConnectedAP of IED AP and no redundant PhysConn on same AP 06/21/2022 09:28 AM Actions
534 IEC 61850 User Feedback Task Force Feature 15 IOP_2017/24 Closed Normal

IEC 61850-6, IEC 61850-7-2

A GCB or MSVCB can only have one single control block address entry in the whole communication section 06/21/2022 09:24 AM Actions
500 IEC 61850 User Feedback Task Force Support 15 IOP_2015 Closed Normal

6

2.2. BufMod is optional for ReportControl. No default value provided by the schema. SCT is interpreting as unbuffered only. Com 06/21/2022 09:12 AM Actions
424 IEC 61850 User Feedback Task Force Support 15 ENTSO-E Closed Normal

6

Vendor Tools shall allow (vendor independant) Integration tools doing engineering based on ICD Files, thus allowing them to in 12/06/2022 09:01 AM Actions
458 IEC 61850 User Feedback Task Force Bug 15 IOP_2013 Closed High

IEC 61850-6

ICD issue when cBName="fix" but not all the RCBs has been declared 02/11/2021 06:15 AM Actions
587 IEC 61850 User Feedback Task Force Feature 1404 IOP_2019 Closed Normal

IEC 61850-6

LNodeTypes and DOTypes not used in the IED section - is it allowed to keep them in DataTypeTemplate section? 02/11/2021 07:01 AM Actions
533 IEC 61850 User Feedback Task Force Support 14 IOP_2017/23 Closed Normal MSVID shall be unique. The integrated application SCD file allowed duplicate SVID’s for two merging units. 06/21/2022 09:13 AM Actions
499 IEC 61850 User Feedback Task Force Support 14 IOP_2015 Closed Normal

6

Issue 4 – Private section – namespace moved from SCL node to Private nodes ICT added the namespace within the privates instead o 06/21/2022 09:12 AM Actions
457 IEC 61850 User Feedback Task Force Feature 14 IOP_2013 Closed Normal

IEC 61850-6

A SCL file is created without maxAttributes attribute defined. What does it mean semantically it the attr. is missing? 02/11/2021 07:46 AM Actions
423 IEC 61850 User Feedback Task Force Support 14 ENTSO-E Closed Normal Conformance test for SICS. 02/11/2021 07:47 AM Actions
586 IEC 61850 User Feedback Task Force Feature 1340 IOP_2019 Closed Normal

IEC 61850-6

Client application cannot connect to IED that are having issue with format of AP-Title 07/05/2022 08:26 AM Actions
585 IEC 61850 User Feedback Task Force Feature 1337 IOP_2019 Closed Normal

IEC 61850-6

SCT unable to configure the device to communicate on multiple subnets due to having a single AP (with all Eth. Ports) 07/05/2022 08:24 AM Actions
532 IEC 61850 User Feedback Task Force Feature 13 IOP_2017/22 Closed Normal

IEC 61850-7-2

An implementation do not allow BRCB resvTms to be written while rptEnable is True 06/21/2022 09:24 AM Actions
498 IEC 61850 User Feedback Task Force Support 13 IOP_2015 Closed Normal

6

Issue 3 – GoCB confRev - behaviour if ConfRev=“0“ IED rejected that value. 7-2: If there are inconsistent attribute values in t 06/21/2022 09:12 AM Actions
456 IEC 61850 User Feedback Task Force Support 13 IOP_2013 Closed Normal A client only ICD did not have a ClientServices section. An SCT imported the file and assigned used the IED to reserve a RCB wit 06/21/2022 09:00 AM Actions
422 IEC 61850 User Feedback Task Force Support 13 ENTSO-E Closed Normal Mapping utility signals to IEC 61850 objectcs from specification perspective 06/05/2023 01:59 AM Actions
531 IEC 61850 User Feedback Task Force Feature 12 IOP_2017/21 Closed Normal

IEC 61850-8-1, IEC 61850-9-2

Merging Unit is not capable to publish SV outside of the recommended destination MAC address range (even though 8-1 is informative) 06/21/2022 09:24 AM Actions
497 IEC 61850 User Feedback Task Force Support 12 IOP_2015 Closed Normal

6

Issue 2 - IED restrictions not known by SCT 2.1 IED support 50% URCB and 50% BRCB Service section provide a total RCB number 2. 06/21/2022 09:12 AM Actions
455 IEC 61850 User Feedback Task Force Feature 12 IOP_2013 Closed Normal How does a SCT know the maximum number of instantiated RCBs allowed in an IED and what the allowed distribution per RCB? 02/11/2021 07:47 AM Actions
421 IEC 61850 User Feedback Task Force Support 12 ENTSO-E Closed Normal

IEC 61850-4

Project management as proposed by IEC61850-4 is not supported by commercially available tools 06/05/2023 01:59 AM Actions
584 IEC 61850 User Feedback Task Force Feature 1122 IOP_2019 Closed Normal

IEC 61850-6

SCL validation - Should all name parts of PhV be contained in the doName? 05/09/2023 09:12 AM Actions
530 IEC 61850 User Feedback Task Force Feature 11 IOP_2017/20 Closed Normal

IEC 61850-6

SCT is passing ICD errors to SCD. 06/21/2022 09:24 AM Actions
496 IEC 61850 User Feedback Task Force Support 11 IOP_2015 Closed Normal

6

DUSTIN: Issue 3: Symmetrical Bindings of DA In case of late Binding at DO/DA Level. IED expects DO at later binding, but source 06/21/2022 09:12 AM Actions
420 IEC 61850 User Feedback Task Force Support 11 ENTSO-E Closed Normal Procedures to establish client / server communications should be defined 06/05/2023 01:59 AM Actions
454 IEC 61850 User Feedback Task Force Bug 11 IOP_2013 Closed High Data model: extension of logical nodes with new DOs. Question about namespace. 02/09/2021 06:16 AM Actions
419 IEC 61850 User Feedback Task Force Support 10.2 ENTSO-E Closed Normal

IEC 61850-7-2

Also many other features of GOOSE messaging are left to the manufacturer to choose. 12/06/2022 09:01 AM Actions
418 IEC 61850 User Feedback Task Force Support 10.1 ENTSO-E Closed Normal

IEC 61850-6

DataSets for GOOSE messaging - modeling with: only DA, only DO or both? 02/11/2021 08:02 AM Actions
529 IEC 61850 User Feedback Task Force Feature 10 IOP_2017/16 Closed Normal

IEC 61850-6

SCT imports ICD with SGCB, and the settings with FC= SP outside this setting group are changed to FC=SE in the exported DOType part 06/21/2022 09:24 AM Actions
495 IEC 61850 User Feedback Task Force Support 10 IOP_2015 Closed Normal

6

Issue 2: SCT Behavior When Revising/Replacing IED Configuration Between SCT Tools In terms of the data model structure and comm 06/21/2022 09:12 AM Actions
453 IEC 61850 User Feedback Task Force Bug 10 IOP_2013 Closed High

IEC 61850-6

ExtRef definition and the expected semantic of intAddr 02/11/2021 06:17 AM Actions
520 IEC 61850 User Feedback Task Force Support 1 IOP_2017/1 Closed Normal IEC 61850-6 leaves the definition of the meaning of the authentication options to the SCSM. However, neither 8-1 nor IEC 62351-6 06/21/2022 09:13 AM Actions
486 IEC 61850 User Feedback Task Force Support 1 IOP_2015 Closed Normal

7-1, 7-4

An ICT has required LGOS configuration coming from SCT to be able to subscribe GOOSE. Is it the way it should work? And is it re 06/21/2022 09:11 AM Actions
444 IEC 61850 User Feedback Task Force Bug 1 IOP_2013 Closed High Mixing ed1 and ed2 data models in an ed2 SCL file. 02/09/2021 06:18 AM Actions
403 IEC 61850 User Feedback Task Force Bug 1 ENTSO-E Closed High Problem exchanging SCL file between tools 02/09/2021 06:22 AM Actions
5043 WG13 Issues CIM Issues Closed Low JCIMClean found 3 CIM association ends that should be singu 10/20/2023 01:18 PM Actions
5042 WG13 Issues CIM Issues Closed Low JCIMClean found 215 CIM association ends that should be plu 10/20/2023 01:25 PM Actions
5041 WG13 Issues CIM Issues Closed Low JCIMClean found 2 association ends whose name contains ille 10/20/2023 01:25 PM Actions
5040 WG13 Issues CIM Issues Closed Low JCIMClean found 6 informative associations missing informat 10/20/2023 01:24 PM Actions
5039 WG13 Issues CIM Issues Closed Low JCIMClean found 46 associations that have same documentatio 10/20/2023 01:24 PM Actions
5038 WG13 Issues CIM Issues Closed Low 18 CIM attributes whose name starts with the name of contai 10/20/2023 01:24 PM Actions
5037 WG13 Issues CIM Issues Closed Low JCIMClean found 71 CIM attributes that should be singular - 10/20/2023 01:23 PM Actions
5036 WG13 Issues CIM Issues Closed Low JCIMClean found 18 CIM attributes whose name starts with an 10/20/2023 01:23 PM Actions
5035 WG13 Issues CIM Issues Closed Low JCIMClean found 1 attributes (whose type is enumerated type 10/20/2023 01:23 PM Actions
5034 WG13 Issues CIM Issues Closed Low JCIMClean found 7 attributes that have word 'flag'. - renam 10/20/2023 01:22 PM Actions
5033 WG13 Issues CIM Issues Closed Low JCIMClean found 2 CIM attributes that are not 'static const 10/20/2023 01:22 PM Actions
5032 WG13 Issues CIM Issues Closed Low JCIMClean found 18 CIM classes never used as type for attri 10/20/2023 01:22 PM Actions
5031 WG13 Issues CIM Issues Closed Low JCIMClean found 1 enum classes that have some codes, but no 10/20/2023 01:21 PM Actions
5030 WG13 Issues CIM Issues Closed Low JCIMClean found 11 CIM classes that should be singular - re 10/20/2023 01:21 PM Actions
5029 WG13 Issues CIM Issues Closed Low JCIMClean found 7 classes whose documentation does not end 10/20/2023 01:21 PM Actions
5028 WG13 Issues CIM Issues Closed Low JCIMClean Found 1 CIM datatype classes that should have at 10/20/2023 01:20 PM Actions
5027 WG13 Issues CIM Issues Closed Low JCIMClean Found 4 CIM classes never used in any association 10/20/2023 01:20 PM Actions
5026 WG13 Issues CIM Issues Closed Low JCIMClean Found 23 enumeration classes with bad name: name 10/20/2023 01:20 PM Actions
5025 WG13 Issues CIM Issues Closed Low JCIMClean Found 10 packages with unexpected embedded elemen 10/20/2023 01:19 PM Actions
4944 WG13 Issues CIM Issues Closed Low Combining bus-branch and breaker-nodemodels is unclear. Th 02/07/2023 01:57 PM Actions
4941 WG13 Issues CIM Issues Closed Low Equipment.aggregate on GeneratingUnit only to avoid redundancy 10/11/2023 10:37 AM Actions
4938 WG13 Issues CIM Issues Closed Low qPccControl missing for CSCTwo possibilities should be ava 02/07/2023 01:36 PM Actions
4936 WG13 Issues CIM Issues Closed Low Unclear hydroplant modelThe class HydroPlant is partly ove 10/03/2023 03:24 AM Actions
4934 WG13 Issues CIM Issues Closed Low Modelling of PotentialTransformer and CurentTransformer 10/20/2023 10:11 AM Actions
4932 WG13 Issues CIM Issues Closed Low Scheduled generation splitSpecify how the scheduled genera 10/03/2023 03:23 AM Actions
4931 WG13 Issues CIM Issues Closed Low Specification of equipment for network analysisIt is commo 02/07/2023 01:25 PM Actions
4930 WG13 Issues CIM Issues Closed Low ENTSO-E 13 - EquivalentInjection support WardEquivalentInj 02/07/2023 01:22 PM Actions
4929 WG13 Issues CIM Issues Closed Low ENTSO-E 12 - SynchronousMachine PU Some attributes need to 02/07/2023 01:19 PM Actions
4928 WG13 Issues CIM Issues Closed Low ENTSO-E 9 TapChanger ltcFlag confusingThe note "The attrib 02/07/2023 01:12 PM Actions
(201-300/3050) Per page: 25, 50, 100