Support #487
In the service section, there is the new element “client services”. That element includes GOOSE (default FALSE). Is it required
Status:
Closed
Priority:
Normal
Assignee:
-
Category:
-
Start date:
Due date:
% Done:
0%
Estimated time:
ID:
2
Source:
IOP_2015
TF Unique ID:
2 # IOP_2015
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
To discuss in WG10:
Short Proposal:
TISSUE to be written by The Bruce.
(In Part 6, GOOSE subscriber, not client.)
Standard(s):
6
Needs More Information:
Assigned TF:
Description
In the service section, there is the new element “client services”. That element includes GOOSE (default FALSE). Is it required that every icd/iid file of a server (only), that supports GOOSE subscription, requires that element to be there? If missing, can a system tool assume that it cannot configure GOOSE messages to be sent to that device?
Issue centers around fix or conf referring to all CBs & datasets. Is per-CB attribute needed?
If cbName = fix is CB deletable ?
Updated by Carlos Rodriguez del Castillo almost 2 years ago
- Status changed from New to Closed
Confirm to IEC 61850-6 editor that this issue has been accounted for.