Project

General

Profile

Support #487

In the service section, there is the new element “client services”. That element includes GOOSE (default FALSE). Is it required

Added by Herbert Falk over 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
-
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
2
Source:
IOP_2015
TF Unique ID:
2 # IOP_2015
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
To discuss in WG10:
Short Proposal:

TISSUE to be written by The Bruce.
(In Part 6, GOOSE subscriber, not client.)

Standard(s):

6

Needs More Information:
Assigned TF:

Description

In the service section, there is the new element “client services”. That element includes GOOSE (default FALSE). Is it required that every icd/iid file of a server (only), that supports GOOSE subscription, requires that element to be there? If missing, can a system tool assume that it cannot configure GOOSE messages to be sent to that device?

Issue centers around fix or conf referring to all CBs & datasets. Is per-CB attribute needed?
If cbName = fix is CB deletable ?

#1

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Status changed from New to Closed

Confirm to IEC 61850-6 editor that this issue has been accounted for.

Also available in: Atom PDF