01/14/2025
- 08:52 AM IEC 61850 User Feedback Task Force Improvement #7095 (In Progress): DO "CECtl" and "Auto" of LN CCGR share a close semantic description
- We need an explanation from 90-14 of the difference between "CECtl" and "Auto" because the descriptions are quite sim...
- 08:43 AM IEC 61850 User Feedback Task Force Improvement #7094 (Triage): Add MotV (Motor Voltage) to LN SOPM
- We need a use case where Motor Voltage is needed.
- 08:41 AM IEC 61850 User Feedback Task Force Improvement #7093 (Resolved): Attribute type of SmpRate is not sufficient for Travelling Wave application
- Nothing else we can do in this TF UF, it is already captured in the tissue database for future improvement (Ed3).
- 08:32 AM IEC 61850 User Feedback Task Force Improvement #7092 (Resolved): Missing DO in LN PSCH
- We recommend closing the tissue #1943 as it is not an InterOp.
Our recommendation is to modify the description of "D... - 08:19 AM IEC 61850 User Feedback Task Force Feature #7032 (Resolved): Addition of a DO in XCBR indicating that the contacts have started to separate
- Recommendation from TFUF is to address this issue by the TF that is doing the revision of IEC 61850-90-3 (Alexander W...
11/19/2024
- 08:07 AM IEC 61850 User Feedback Task Force Improvement #7039 (Closed): Simulation bit for test systems
- 7-1 section 7.8.2 Figure 40 refers as "Simulation device" the device that is sending simulation Goose
7-2 Table 94 a...
10/22/2024
- 09:37 AM IEC 61850 User Feedback Task Force Improvement #6992 (Resolved): Add identifier to KDC
- We hade feedback:
"No practical use case regarding that. It`s only an improvement request, because according to Stan... - 09:23 AM IEC 61850 User Feedback Task Force Feature #7033 (Resolved): Addition of DO SPS in the LN KPMP
- Inform to Alexander Winterer about this issue for his task force.
- 09:18 AM IEC 61850 User Feedback Task Force Feature #7032 (Triage): Addition of a DO in XCBR indicating that the contacts have started to separate
- We need more information about why we would need a new DO.
We will have anyway to check abbreviations from 7-4 since... - 09:09 AM IEC 61850 User Feedback Task Force Bug #7030 (Resolved): Is there a use case for applying more than one trgOpt on a particular DA?
- We could not find a use case where having both trigger conditions set for a given data attribute (DA) would make sens...