Support #497

Issue 2 - IED restrictions not known by SCT 2.1 IED support 50% URCB and 50% BRCB Service section provide a total RCB number 2.

Added by Herbert Falk about 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
-
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
12
Source:
IOP_2015
TF Unique ID:
12 # IOP_2015
WG10 Proposal:

TISSUE 1448

Estimated Completion:
Discuss in Upcoming Meeting:
To discuss in WG10:
Short Proposal:

Issue 2.1: Allowed limitation need to be addressed in ED 2.1
Need to add a differentiation between URCB and BRCB in SCL 2.1: need to be able to indicate the limit on BRCB vs. URCBs? E.g., ConfReportControl.maxBuf (optional, no default; if not specified means can be up to max; cannot be greater than max). May only be defined (present) if bufMod = both.
Herb to write a tissue (should be for Ed. 2.1).

Issue 2.2: Recommendation that limitation be confirmed by WG10.
See “SCL_Brunner_x_20150927_CtlModelDecl”.
If all controllables must have the same ctlModel value, then this is only allowed if all ctlModels are read-only (can only be set in the ICT) => all ctlModel DAs have valKind=RO and valImport=false.
? Thus, described situation is not allowed.
There is no DA defining the control model of a whole device.

Standard(s):

6

Needs More Information:
Assigned TF:

Description

Issue 2 - IED restrictions not known by SCT
2.1 IED support 50% URCB and 50% BRCB
Service section provide a total RCB number
2.2 Ctlmodel
ICT vendor have a single Ctlmodel for the full IED. This limitation is not specified.

#1

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Status changed from New to Closed

Confirm to IEC 61850-6 editor that this issue has been accounted for.