Feature #534

A GCB or MSVCB can only have one single control block address entry in the whole communication section

Added by Herbert Falk about 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Standard extension required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
15
Source:
IOP_2017/24
TF Unique ID:
15 # IOP_2017/24
WG10 Proposal:

reference added is more generic, indicating that rule for communication aspect has to be considered while reading the part 6-> OK: Specified in 6, 7-2 Table 2

Estimated Completion:
(2019-06) No target date was set.
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:

Refer to WG10.Suggest adding reference to 7-2 Table 1 Note which states:” All the services for spontaneous sending are limited to one access point per control block instance” for 9.4.4 and 9.4.5.

Standard(s):

IEC 61850-6, IEC 61850-7-2

Needs More Information:
Assigned TF:

Description

SCD import of IntegratedApplication.scdHVv5 to ICT generated the following error:

A GOOSE or Sampled Value Control Block can only have one single control block address entry in the whole communication section. Adding a second control block address was denied for GoCB Name='gcb1' Description='BreakerControl' Ref='GE_C264_LINE_1CONTROL/LLN0.gcb1'

The two AP’s are connected to different subnets, but they belong to the same IED.

#1

Updated by Vladan Cvejic about 3 years ago

  • Subject changed from SCD import of IntegratedApplication.scdHVv5 to ICT generated the following error: A GOOSE or Sampled Value Control Block can on to A GCB or MSVCB can only have one single control block address entry in the whole communication section
  • Status changed from New to In Progress
  • Short Proposal changed from Refer to WG10. Suggest adding reference to 7-2 Table 1 Note which states:” All the services for spontaneous sending are limited to one access point per control block instance” for 9.4.4 and 9.4.5. to Refer to WG10.Suggest adding reference to 7-2 Table 1 Note which states:” All the services for spontaneous sending are limited to one access point per control block instance” for 9.4.4 and 9.4.5.
  • Standard(s) changed from 6,7-2 to IEC 61850-6, IEC 61850-7-2
  • WG10 Proposal changed from reference added is more generic, indicating that rule for communication aspect has to be considered while reading the part 6 -> OK (2019-06): Specified in 6, 7-2 Table 2 to reference added is more generic, indicating that rule for communication aspect has to be considered while reading the part 6-> OK(2019-06): Specified in 6, 7-2 Table 2
  • Discuss in Upcoming Meeting set to No

Checking done.

#2

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Status changed from In Progress to Closed

Confirm to IEC 61850-6 editor that this issue has been accounted for.