Project

General

Profile

Support #503

Issue 1: History section is present in ICD but during import SCT is discarding this history section. Also, maintenance of histor

Added by Herbert Falk about 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
-
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
18
Source:
IOP_2015
TF Unique ID:
18 # IOP_2015
WG10 Proposal:

DE06 german comment

Estimated Completion:
Discuss in Upcoming Meeting:
To discuss in WG10:
Short Proposal:

When is this history needed?
Not history, but version/revision information from the last IxD.

Proposal: add two attributes to IED matching the SCL/Header.version (and revision) of the last imported IxD.
=> Optional ixdVersion and ixdRevision attributes on IED, shall be set in the SCD/SED by SCT upon import of an IxD. ICT can remove that information from IxD it exports, if present, must be the same as the IxD History.version and revision attributes.

Also: in IxD file we need to “remember” the last SCD imported. (Different set of attributes)
=> Optional attributes scdVersion and scdRevision on IED element, shall be set in the IxD by ICT, and imported by SCT as is.

SCT shall indicate in the SCD which IEDs were modified…

Conclusion: Thierry, Herb, and Chris to make a proposal for next WG10 October meeting.

Standard(s):

6

Needs More Information:
Assigned TF:

Description

Issue 1:
History section is present in ICD but during import SCT is discarding this history section.
Also, maintenance of history section revisions during import of several ICD/IID files has to be addressed.

#1

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Status changed from New to Closed

Confirm to IEC 61850-6 editor that this issue has been accounted for.

Also available in: Atom PDF