Support #504
When IID file from ICT includes “mustUnderstand” attribute in <GSEcontrol> such as <GSEControl desc="System Logical Device GOOS
0%
it was done CDV amendment 2.1 part 6
(2015-10-15): Thierry, Camille, Chris
The order of elements in SCL is clearly defined in the SCL schema, so no additional clarification is needed.
Nonetheless, Part 6 should include an example showing the usage of the mustUnderstand attribute (with GSEControl/Protocol) for clarification.
6
Description
When IID file from ICT includes “mustUnderstand” attribute in <GSEcontrol> such as
<GSEControl desc="System Logical Device GOOSE Control Block 1" name="gcb01" datSet="ds_gcb1" confRev="10000" appID="AA1D1Q01KF1System/LLN0gcb01">
<Protocol mustUnderstand="true" />
</GSEControl>
where is the proper order to add <IEDName> attribute? Prior to it, or the next to it? In general case, bottom or top? If tool checks the appropriate attribute order according to schema, it could be issue.
Updated by Carlos Rodriguez del Castillo almost 2 years ago
- Status changed from New to Closed
Confirm to IEC 61850-6 editor that this issue has been accounted for.