Support #504
When IID file from ICT includes “mustUnderstand” attribute in <GSEcontrol> such as <GSEControl desc="System Logical Device GOOS
0%
it was done CDV amendment 2.1 part 6
(2015-10-15): Thierry, Camille, Chris
The order of elements in SCL is clearly defined in the SCL schema, so no additional clarification is needed.
Nonetheless, Part 6 should include an example showing the usage of the mustUnderstand attribute (with GSEControl/Protocol) for clarification.
6
Description
When IID file from ICT includes “mustUnderstand” attribute in <GSEcontrol> such as
<GSEControl desc="System Logical Device GOOSE Control Block 1" name="gcb01" datSet="ds_gcb1" confRev="10000" appID="AA1D1Q01KF1System/LLN0gcb01">
<Protocol mustUnderstand="true" />
</GSEControl>
where is the proper order to add <IEDName> attribute? Prior to it, or the next to it? In general case, bottom or top? If tool checks the appropriate attribute order according to schema, it could be issue.