Project

General

Profile

Support #456

A client only ICD did not have a ClientServices section. An SCT imported the file and assigned used the IED to reserve a RCB wit

Added by Herbert Falk about 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
-
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
13
Source:
IOP_2013
TF Unique ID:
13 # IOP_2013
WG10 Proposal:

Verify in the -4 document there is a recommendation.

Estimated Completion:
Discuss in Upcoming Meeting:
To discuss in WG10:
Short Proposal:

[Issue is restricted to Ed1 device in edition 2 SCL files and should not be resolved in isolation to other issues related to ED.1 and ED.2 co-residence in a single (Ed.2) SCD file.]

Wait for Regina meeting.

Standard(s):
Needs More Information:
Assigned TF:

Description

A client only ICD did not have a ClientServices section. An SCT imported the file and assigned used the IED to reserve a RCB without validation.
In ED.1, there was no ClientServices. Ed.2 added this to the SCL. Therefore, this could be an issue to resolve in ED.1 and ED.2 co-residence in a single SCD (see SCL issue 1).
Within the context of ED.2, the ClientServices should be present ,although marked as not being required for backward compatibility. In this case an interoperability profile needs to be developed.

#1

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Status changed from New to Closed

Also available in: Atom PDF