Feature #529

SCT imports ICD with SGCB, and the settings with FC= SP outside this setting group are changed to FC=SE in the exported DOType part

Added by Herbert Falk about 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Standard extension required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
10
Source:
IOP_2017/16
TF Unique ID:
10 # IOP_2017/16
WG10 Proposal:

short proposal implemented -> OK: Specified in 6 Ed2.1 section 9.5.1

Estimated Completion:
(2019-06) No target date was set.
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:

FC=SP means Setting (outside setting group). The attribute is mandatory, if this data shall be a setting outside a setting group (IEC61850-6 Chapter 5).The SCT shall not change any function constraint of the ICD file.Suggest adding text around INF 3850-3859: SCT may change the name/id of LNodeType, DAType, etc. found in the DataTypeTemplate section. The SCT shall not change the underlying definitions unless specified by an upgrade/downgrade rule.

Standard(s):

IEC 61850-6

Needs More Information:
Assigned TF:

Description

The integrated application area SCD (IntegratedApplicationv4.2_2007B.SCD) was created by importing an ICD which LD (PROT) has a SGCB in LLN0. But the settings with FC= SP outside this setting group was changed to FC=SE in the exported DOType part.
If the constraint change is correct in the SCD, there is also another problem that the fc attribute of <FCDA/> of the same settings in DataSet are still SP.

#1

Updated by Vladan Cvejic about 3 years ago

  • Subject changed from The integrated application area SCD (IntegratedApplicationv4.2_2007B.SCD) was created by importing an ICD which LD (PROT) has a to SCT imports ICD with SGCB, and the settings with FC= SP outside this setting group are changed to FC=SE in the exported DOType part
  • Status changed from New to In Progress
  • Short Proposal changed from FC=SP means Setting (outside setting group). The attribute is mandatory, if this data shall be a setting outside a setting group (IEC61850-6 Chapter 5). The SCT shall not change any function constraint of the ICD file. Suggest adding text around INF 3850-3859: SCT may change the name/id of LNodeType, DAType, etc. found in the DataTypeTemplate section. The SCT shall not change the underlying definitions unless specified by an upgrade/downgrade rule. to FC=SP means Setting (outside setting group). The attribute is mandatory, if this data shall be a setting outside a setting group (IEC61850-6 Chapter 5).The SCT shall not change any function constraint of the ICD file.Suggest adding text around INF 3850-3859: SCT may change the name/id of LNodeType, DAType, etc. found in the DataTypeTemplate section. The SCT shall not change the underlying definitions unless specified by an upgrade/downgrade rule.
  • Standard(s) changed from 6 to IEC 61850-6
  • WG10 Proposal changed from short proposal implemented -> OK (2019-06): Specified in 6 Ed2.1 section 9.5.1 to short proposal implemented -> OK(2019-06): Specified in 6 Ed2.1 section 9.5.1
  • Discuss in Upcoming Meeting set to No

Checking done.

#2

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Status changed from In Progress to Closed

Confirm to IEC 61850-6 editor that this issue has been accounted for.