Feature #540

Some SCT tools are removing incomplete Inputs with ExtRef’s of serviceType=”SMV” that are used for late binding of sample values

Added by Herbert Falk about 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Standard extension required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
21
Source:
IOP_2017/35
TF Unique ID:
21 # IOP_2017/35
WG10 Proposal:

add statement in ExtRef description to not allow removing of ExtRef with intAddr defined-> OK: Specified in part 6

Estimated Completion:
(2019-06) No target date was set.
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:

Refer to WG10Table 35, and its text, needs to be modified to state that ExtRefs shall not be removed by the SCT as if the value of intAddr is not “null”.

Standard(s):

IEC 61850-6

Needs More Information:
Assigned TF:

Description

Some SCT tools are removing incomplete Inputs with ExtRef’s of serviceType=”SMV” that are used for late binding of sample values in all versions of the IntegratedApplicationHV.scd file.

#1

Updated by Vladan Cvejic about 3 years ago

  • Status changed from New to In Progress
  • Short Proposal changed from Refer to WG10 Table 35, and its text, needs to be modified to state that ExtRefs shall not be removed by the SCT as if the value of intAddr is not “null”. to Refer to WG10Table 35, and its text, needs to be modified to state that ExtRefs shall not be removed by the SCT as if the value of intAddr is not “null”.
  • Standard(s) changed from 6 to IEC 61850-6
  • WG10 Proposal changed from add statement in ExtRef description to not allow removing of ExtRef with intAddr defined -> OK (2019-06): Specified in part 6 to add statement in ExtRef description to not allow removing of ExtRef with intAddr defined-> OK(2019-06): Specified in part 6
  • Discuss in Upcoming Meeting set to No

Checking done.

#2

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Status changed from In Progress to Closed

Confirm to IEC 61850-6 editor that this issue has been accounted for.