Support #538

SCT engineering problems

Added by Herbert Falk over 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Implementation - improve conformance testing
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
19
Source:
IOP_2017/29
TF Unique ID:
19 # IOP_2017/29
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:

No action required by WG10 except to publish the AMD-1.

Standard(s):

IEC 61850-6

Needs More Information:
Assigned TF:

Description

Problem 1: SCT Removed Privates that were provided in ICD that should have not been removed.
Implementation

Problem 2: SCT added Extrefs even though the ICD did not provide partial Extrefs.
Refer to standard – how to identify constraints.

Problem 3: SCT did not add subscriptions (e.g. IEDName) for the GOOSE that was specified in the ExtRefs.
Ed2.1 requirement, OK for Ed2.

Problem 4: ICD did not provide partial Extrefs.
OK, this is optional per CB.

File names involved were: MU02 V4.02 Side 2.icd and IOP_LV_v4_All.scd.

#1

Updated by Vladan Cvejic about 3 years ago

  • Subject changed from Problem 1: SCT Removed Privates that were provided in ICD that should have not been removed. Implementation Problem 2: SCT adde to SCT engineering problems
  • Category set to Implementation - improve conformance testing
  • Status changed from New to In Progress
  • Standard(s) set to IEC 61850-6
  • Discuss in Upcoming Meeting set to No

Checking done.

#2

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Status changed from In Progress to Closed

Confirm to IEC 61850-6 editor that this issue has been accounted for.