Feature #530
SCT is passing ICD errors to SCD.
0%
Add reference to part 7-1 §14 in part 6 §9.5.1 (datatype template) to indicate that datamodel restriction is defined by 7-1 -> OK: Specified in 6 Ed2.1 section 9.5.1
Where in the engineering workflow is SCL validation required?Suggest adding text from 7-1 14.5.4 restricting the extension of CDCs to somewhere in -6 lines 327-329 or add a direct reference to the clause in 7-1.
IEC 61850-6
Description
V4.1 of the SCD file contains an invalid device;
1. The T2WPDIF logical contains DOs of TotW, TotVAr, TotVA, TotPF, Hz and PhV
2. The timestamp for the MV associated with the TotX and Hz elements is in the ST functional constraint.
These errors are in the ICD file. Seems like an SCT should have prevented this from being passed to the SCD?
Updated by Vladan Cvejic over 3 years ago
- Subject changed from V4.1 of the SCD file contains an invalid device; 1. The T2WPDIF logical contains DOs of TotW, TotVAr, TotVA, TotPF, Hz and PhV to SCT is passing ICD errors to SCD.
- Status changed from New to In Progress
- Short Proposal changed from Where in the engineering workflow is SCL validation required? Suggest adding text from 7-1 14.5.4 restricting the extension of CDCs to somewhere in -6 lines 327-329 or add a direct reference to the clause in 7-1. to Where in the engineering workflow is SCL validation required?Suggest adding text from 7-1 14.5.4 restricting the extension of CDCs to somewhere in -6 lines 327-329 or add a direct reference to the clause in 7-1.
- Standard(s) changed from 6 to IEC 61850-6
- WG10 Proposal changed from Add reference to part 7-1 §14 in part 6 §9.5.1 (datatype template) to indicate that datamodel restriction is defined by 7-1 -> OK (2019-06): Specified in 6 Ed2.1 section 9.5.1 to Add reference to part 7-1 §14 in part 6 §9.5.1 (datatype template) to indicate that datamodel restriction is defined by 7-1 -> OK(2019-06): Specified in 6 Ed2.1 section 9.5.1
- Discuss in Upcoming Meeting set to No
Checking done.
Updated by Carlos Rodriguez del Castillo over 2 years ago
- Status changed from In Progress to Closed
Confirm to IEC 61850-6 editor that this issue has been accounted for.