Feature #600
Connect the ExtRef - different supported mechanisms by ICT
Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Implementation - improve conformance testing
Start date:
Due date:
% Done:
0%
Estimated time:
ID:
1947
Source:
IOP_2019
TF Unique ID:
1947 # IOP_2019
WG10 Proposal:
Has been clarified in IEC 61850-7-1 Ed2.1 Annex H
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:
ICT issue
Standard(s):
IEC 61850-7-1
Needs More Information:
Assigned TF:
Description
Various ICT support different mechanisms where a SCT must connect the ExtRef, including:
- A dedicated GGIO LN
- A InRef at LN LGOS
But icd files do not declare noIctBinding
Connecting through an InRef does not seem the right approach.
Requiring dedicated places to bind, from Ed 2.1 on requires the declaration of noIctBinding
Updated by Vladan Cvejic over 3 years ago
- Subject changed from Various ICT support different mechanisms where a SCT must connect the ExtRef, including: - A dedicated GGIO LN - A InRef at LN L to Connect the ExtRef - different supported mechanisms by ICT
- Status changed from New to In Progress
- Standard(s) changed from 1-Jul to IEC 61850-7-1
- Discuss in Upcoming Meeting set to No
Checking done
Updated by Carlos Rodriguez del Castillo over 2 years ago
- Status changed from In Progress to Closed
Confirm to IEC 61850-6 editor the issue has been accounted for