Project

General

Profile

Feature #600

Connect the ExtRef - different supported mechanisms by ICT

Added by Herbert Falk about 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Implementation - improve conformance testing
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
1947
Source:
IOP_2019
TF Unique ID:
1947 # IOP_2019
WG10 Proposal:

Has been clarified in IEC 61850-7-1 Ed2.1 Annex H

Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:

ICT issue

Standard(s):

IEC 61850-7-1

Needs More Information:
Assigned TF:

Description

Various ICT support different mechanisms where a SCT must connect the ExtRef, including:
- A dedicated GGIO LN
- A InRef at LN LGOS

But icd files do not declare noIctBinding

Connecting through an InRef does not seem the right approach.
Requiring dedicated places to bind, from Ed 2.1 on requires the declaration of noIctBinding