Project

General

Profile

Issues

Filters

Apply Clear

# Project Tracker ID Source Status Priority Standard(s) Subject Updated
592 IEC 61850 User Feedback Task Force Feature IntApp IOP_2019 Closed Normal Invalid SCL file due to wrong allocation fo GoCBs 06/21/2022 09:29 AM Actions
527 IEC 61850 User Feedback Task Force Support 8 IOP_2017/10 Closed Normal Regarding the Network infrastructure: Some MU/SAMU cannot configure their SV stream to different VLAN ID , fixed to 0 (but can c 06/21/2022 09:13 AM Actions
414 IEC 61850 User Feedback Task Force Support 6.2 ENTSO-E Closed Normal SCD from system integrator not containing comprehensive substation section 02/03/2021 02:42 PM Actions
413 IEC 61850 User Feedback Task Force Support 6 ENTSO-E Closed Normal Substation part in SCL is mostly non existing in manufacturers scd export files and in form that is defined as in Standard. Subs 02/03/2021 02:42 PM Actions
448 IEC 61850 User Feedback Task Force Feature 5 IOP_2013 Closed Normal ICD has a destination MAC address of 00:00:00:00:00. Is this valid for usage? 02/11/2021 07:50 AM Actions
412 IEC 61850 User Feedback Task Force Support 5 ENTSO-E Closed Normal There is a general issue that when we have signals connected to generic inputs, typically it is not possible to associate these 02/03/2021 02:54 PM Actions
485 IEC 61850 User Feedback Task Force Support 41 IOP_2013 Closed Normal Some switches discard the IEEE 802.1Q tag known as VLAN 0 on packets sent/received on the trunk ports. Others discard the packet 06/21/2022 09:00 AM Actions
484 IEC 61850 User Feedback Task Force Support 40 IOP_2013 Closed Normal A question was raised in regards can Report EntryIDs be reused after IED restart. If so, guidance needs to be given for system d 06/21/2022 09:00 AM Actions
410 IEC 61850 User Feedback Task Force Bug 4.2 ENTSO-E Closed High Data models using GGIO when not needed 02/09/2021 06:19 AM Actions
409 IEC 61850 User Feedback Task Force Feature 4.1 ENTSO-E Closed Normal Too loose or non existing guideline for organization of structure tree (construction of each LD, LN etc) 12/06/2022 09:00 AM Actions
483 IEC 61850 User Feedback Task Force Support 39 IOP_2013 Closed Normal A question was raised in regards to the expected behavior of a server/BRCB that has been purged (e.g. no events buffered) and th 06/21/2022 09:00 AM Actions
482 IEC 61850 User Feedback Task Force Support 38 IOP_2013 Closed Normal When should buffering start for a reserved and fully configured BRCB. The discussion was that buffering should probably begin up 06/21/2022 09:00 AM Actions
481 IEC 61850 User Feedback Task Force Support 37 IOP_2013 Closed Normal A question was raised in regards to how a client should resynchronize to receive the last report (Buffered Reporting). The sta 06/21/2022 09:00 AM Actions
480 IEC 61850 User Feedback Task Force Support 36 IOP_2013 Closed Normal A different client made use of a URCB that had been reserved in SCL for use by a different client via ClientLN. Currently, there 06/21/2022 09:00 AM Actions
479 IEC 61850 User Feedback Task Force Support 35 IOP_2013 Closed Normal An SCL file was produced that had a GOOSE DataSet that contained members that had FC=CO and FC=CF. The SCT performing the import 06/21/2022 09:00 AM Actions
518 IEC 61850 User Feedback Task Force Support 34 IOP_2015 Closed Normal Does the SVID character have to be specifically mentioned to be within 10-34 characters? Some of the vendors have implemented th 06/21/2022 09:12 AM Actions
478 IEC 61850 User Feedback Task Force Support 34 IOP_2013 Closed Normal There is currently no mechanism to allow an array member to be added as a DataSet member In the conformance tables of 8-1, alter 06/21/2022 09:00 AM Actions
517 IEC 61850 User Feedback Task Force Support 33 IOP_2015 Closed Normal IEC 61850-9-3 slaves can by design lock themselves to IEEE C37.238 (Power Profile) masters. This is intended behavior, since IEC 06/21/2022 09:12 AM Actions
477 IEC 61850 User Feedback Task Force Support 33 IOP_2013 Closed Normal Throughout the IOP, there was discussion about validation. However, validation has several different levels to it. There is no v 06/21/2022 09:00 AM Actions
516 IEC 61850 User Feedback Task Force Support 32 IOP_2015 Closed Normal Buffered reporting testing – anomaly with resynch (write of entryId failed, but buffered reports still sent). Because of indexe 06/21/2022 09:12 AM Actions
476 IEC 61850 User Feedback Task Force Support 32 IOP_2013 Closed Normal Currently, in SCL, the size of an array is numeric. This could lead to issues of consistency (e.g. one having 32 array elements 06/21/2022 09:00 AM Actions
515 IEC 61850 User Feedback Task Force Support 31 IOP_2015 Closed Normal These test cases assume that a server will send a negative response to an operate to the same value. Some servers will accept th 06/21/2022 09:12 AM Actions
475 IEC 61850 User Feedback Task Force Support 31 IOP_2013 Closed Normal With the renaming of LNTypes, DOTypes, etc., there should be a specification as to the maximum size for these names. The XSD sho 06/21/2022 09:00 AM Actions
474 IEC 61850 User Feedback Task Force Support 30 IOP_2013 Closed Normal Should all SCTs support a substation section and the ability to associate LNodes into that section. 06/21/2022 09:00 AM Actions
408 IEC 61850 User Feedback Task Force Bug 3.2 ENTSO-E Closed High PICS, MICS and other statements documents are not formally defined 02/09/2021 06:20 AM Actions
407 IEC 61850 User Feedback Task Force Feature 3.1 ENTSO-E Closed Normal "Vendor/User” and “Vendor/Vendor” Interoperability list 02/11/2021 06:17 AM Actions
440 IEC 61850 User Feedback Task Force Support 3 Vattenfall Closed Normal The specified sigal has a utility process name independent of used protcol. E.g. "start of distance protection". Also link to a 06/21/2022 09:19 AM Actions
514 IEC 61850 User Feedback Task Force Support 29 IOP_2015 Closed Normal Priority of error checking in controls – i.e. position-reached instead of Blocked-by-switching-hierarchy. The order of checks i 06/21/2022 09:12 AM Actions
473 IEC 61850 User Feedback Task Force Support 29 IOP_2013 Closed Normal An SCL file was provided that had a <Val> for an OctetString value. A question was raised as to the correct format for the value 06/21/2022 09:00 AM Actions
472 IEC 61850 User Feedback Task Force Support 28 IOP_2013 Closed Normal An ED.2 SCT would not import an ED.1 SCL file. This needs to be addressed with rules of transformation and the definition of a s 06/21/2022 09:00 AM Actions
471 IEC 61850 User Feedback Task Force Support 27 IOP_2013 Closed Normal How should an SCL file express the initial value of GOCB.Ena and SVCB.Ena. It would appear that the Control Block schema definit 06/21/2022 09:00 AM Actions
436 IEC 61850 User Feedback Task Force Support 27 ENTSO-E Closed Normal Too many options in the standard 06/05/2023 01:59 AM Actions
470 IEC 61850 User Feedback Task Force Support 26 IOP_2013 Closed Normal An ICT provides an IID/ICD file that defines 4 GOCBs. The SCT imports this file, creates an SCD which has only 1 GOCB. The ICT r 06/21/2022 09:00 AM Actions
435 IEC 61850 User Feedback Task Force Support 26 ENTSO-E Closed Normal Interoperability between vendor products is not verified/certified by UCA 02/11/2021 07:06 AM Actions
469 IEC 61850 User Feedback Task Force Support 25 IOP_2013 Closed Normal The iedType attribute is optional within SCL. However, some SCL tools use this as part of validation. Lack of the attribute/valu 06/21/2022 09:00 AM Actions
434 IEC 61850 User Feedback Task Force Support 25 ENTSO-E Closed Normal Freedom of choice what IEC 61850 services are to be tested seem too open. The vendor can select exactly what UCA accredited test 12/06/2022 09:01 AM Actions
468 IEC 61850 User Feedback Task Force Support 24 IOP_2013 Closed Normal The mechanism for defining a GI attribute in a ED.2 RCB does not validate and import into an ED.1 ICT. 06/21/2022 09:00 AM Actions
467 IEC 61850 User Feedback Task Force Support 23 IOP_2013 Closed Normal There are normative ENUM definitions for 7-4. (e.g. Mod) but there is no guidance in regards to naming rules (e.g. Modkind). 06/21/2022 09:00 AM Actions
432 IEC 61850 User Feedback Task Force Support 23 ENTSO-E Closed Normal There are interoperability problems between client and server IEDs due to product implementation. 02/11/2021 07:33 AM Actions
466 IEC 61850 User Feedback Task Force Support 22 (2) IOP_2013 Closed Normal In a SCD there were LNodes in the substation section that were not associated to a specific IED/LN instance. The question was if 06/21/2022 09:00 AM Actions
465 IEC 61850 User Feedback Task Force Support 22 (1) IOP_2013 Closed Normal In a SCD there were LNodes in the substation section that were not associated to a specific IED/LN instance. In particular, an S 06/21/2022 09:00 AM Actions
507 IEC 61850 User Feedback Task Force Support 22 IOP_2015 Closed Normal If the client reads a SCD file and loads then the data model (or vice versa ???) what data shall a client compare? confRef’s, da 06/21/2022 09:10 AM Actions
464 IEC 61850 User Feedback Task Force Support 21 IOP_2013 Closed Normal There is an issue about differentiation between “fixed” /preconfigured DataSets and those that can be changed in a SCT. Some ICT 06/21/2022 09:00 AM Actions
430 IEC 61850 User Feedback Task Force Support 21 ENTSO-E Closed Normal IED certification needs to include tool interoprability validation 02/11/2021 07:36 AM Actions
406 IEC 61850 User Feedback Task Force Bug 2.3 ENTSO-E Closed High Configuration of datasets by users 02/03/2021 03:55 PM Actions
405 IEC 61850 User Feedback Task Force Feature 2.2 ENTSO-E Closed Normal Optionality of DO/DA from the point of view of users 02/11/2021 06:20 AM Actions
404 IEC 61850 User Feedback Task Force Feature 2.1 ENTSO-E Closed Normal Meaning of "optional" regarding data model 02/11/2021 06:21 AM Actions
462 IEC 61850 User Feedback Task Force Support 19 IOP_2013 Closed Normal The use of ExtRef to subscribe to a SV was questioned. There are several different mechanisms that could be used in 61850-6 to s 06/21/2022 09:00 AM Actions
427 IEC 61850 User Feedback Task Force Support 18 ENTSO-E Closed Normal Functional constrained data shall include all levels of a hierarchy 02/11/2021 07:41 AM Actions
596 IEC 61850 User Feedback Task Force Feature 1710 IOP_2019 Closed Normal An IED declares constraints that are not machine processable 02/11/2021 06:43 AM Actions
536 IEC 61850 User Feedback Task Force Support 17 IOP_2017/26 Closed Normal SCT did not import GOOSE and 3 of the sampled value control blocks that existed in PMU ICD file. This caused validation failures 06/21/2022 09:13 AM Actions
460 IEC 61850 User Feedback Task Force Support 17 IOP_2013 Closed Normal The usage of ClientLN in RptEna is optional. What does this mean. 61850-6 made this option for backward compatibility with ED.1. 06/21/2022 09:00 AM Actions
533 IEC 61850 User Feedback Task Force Support 14 IOP_2017/23 Closed Normal MSVID shall be unique. The integrated application SCD file allowed duplicate SVID’s for two merging units. 06/21/2022 09:13 AM Actions
423 IEC 61850 User Feedback Task Force Support 14 ENTSO-E Closed Normal Conformance test for SICS. 02/11/2021 07:47 AM Actions
456 IEC 61850 User Feedback Task Force Support 13 IOP_2013 Closed Normal A client only ICD did not have a ClientServices section. An SCT imported the file and assigned used the IED to reserve a RCB wit 06/21/2022 09:00 AM Actions
422 IEC 61850 User Feedback Task Force Support 13 ENTSO-E Closed Normal Mapping utility signals to IEC 61850 objectcs from specification perspective 06/05/2023 01:59 AM Actions
455 IEC 61850 User Feedback Task Force Feature 12 IOP_2013 Closed Normal How does a SCT know the maximum number of instantiated RCBs allowed in an IED and what the allowed distribution per RCB? 02/11/2021 07:47 AM Actions
454 IEC 61850 User Feedback Task Force Bug 11 IOP_2013 Closed High Data model: extension of logical nodes with new DOs. Question about namespace. 02/09/2021 06:16 AM Actions
420 IEC 61850 User Feedback Task Force Support 11 ENTSO-E Closed Normal Procedures to establish client / server communications should be defined 06/05/2023 01:59 AM Actions
444 IEC 61850 User Feedback Task Force Bug 1 IOP_2013 Closed High Mixing ed1 and ed2 data models in an ed2 SCL file. 02/09/2021 06:18 AM Actions
403 IEC 61850 User Feedback Task Force Bug 1 ENTSO-E Closed High Problem exchanging SCL file between tools 02/09/2021 06:22 AM Actions
520 IEC 61850 User Feedback Task Force Support 1 IOP_2017/1 Closed Normal IEC 61850-6 leaves the definition of the meaning of the authentication options to the SCSM. However, neither 8-1 nor IEC 62351-6 06/21/2022 09:13 AM Actions
5045 WG13 Issues CIM Issues Closed High Voltage-dependent reactive capability curve support 02/07/2023 01:24 AM Actions
5011 WG13 Issues CIM Issues Closed High The 61970 452 profile and 456 profile both contain the same 10/20/2023 10:13 AM Actions
5006 WG13 Issues CIM Issues Closed High Overlap between transformer xMin and xThe TransformerEnd.x 02/07/2023 01:37 AM Actions
5004 WG13 Issues CIM Issues Closed High Short circuit data for power electronicsCurrently PowerEle 02/11/2023 01:24 AM Actions
4926 WG13 Issues CIM Issues Closed High TapChangerKind and TransformerControlMode should be dropped 10/20/2023 10:12 AM Actions
4918 WG13 Issues CIM Issues Closed High EnergySource attributes rn and xn should be named r2 and x2 10/20/2023 09:56 AM Actions
4917 WG13 Issues CIM Issues Closed High Documenation of LoadResponseCharacteristic exponents Sugg 02/19/2023 02:38 AM Actions
4915 WG13 Issues CIM Issues Closed High The LoadResponseCharacteristic is different for steady stat 04/12/2023 09:48 AM Actions
6756 General Testing Issues Improvement Closed Normal Should UCA accredit and Certify IEC 61850-3 04/16/2024 08:50 AM Actions
6674 Server Issues Closed Normal Discuss changes to submission form and Certificates 03/01/2024 10:10 AM Actions
5910 Server Issues Closed Normal Need to test that IEDs support 1 Step and 2 Step clocks: IOP 2022 03/01/2024 09:53 AM Actions
5867 WG16 Issues CIM Issues Closed Normal Add meterReadingPeriodicity attribute (String) in the MarketEvaluationPoint class 07/19/2022 05:28 PM Actions
5866 WG16 Issues CIM Issues Closed Normal Add scheduledMeterReadingDate attribute (String) in the MarketEvaluationPoint class 07/19/2022 05:28 PM Actions
5865 WG16 Issues CIM Issues Closed Normal MarketProductType; update description to correct typo 10/13/2023 04:11 PM Actions
5862 WG16 Issues CIM Issues Closed Normal Instructions.instructionType update description 08/08/2022 06:04 PM Actions
5861 WG16 Issues CIM Issues Closed Normal Instructions.bindingDOT change datatype to FloatQuantity 08/08/2022 06:04 PM Actions
5860 WG16 Issues CIM Issues Closed Normal ContractResourceCertificationAgreement update end role names 08/08/2022 06:04 PM Actions
5859 WG16 Issues CIM Issues Closed Normal ResourceCertification update association end role names 08/08/2022 06:03 PM Actions
5858 WG16 Issues CIM Issues Closed Normal Add new association from CommodityDefinition to RegisteredResource 08/08/2022 06:03 PM Actions
5856 WG16 Issues CIM Issues Closed Normal Request for an self-association on AccountingPoint 10/13/2023 04:11 PM Actions
5855 WG16 Issues CIM Issues Closed Normal Request for an association between MarketEvaluationPoint and MarketAgreement 10/13/2023 04:11 PM Actions
5854 WG16 Issues CIM Issues Closed Normal Request for an association between MarketEvaluationPoint and MarketParticipant 10/13/2023 04:11 PM Actions
5853 WG16 Issues CIM Issues Closed Normal Request for an association between MarketEvaluationPoint and Domain 10/13/2023 04:11 PM Actions
5852 WG16 Issues CIM Issues Closed Normal Request for an association between AccountingPoint and DateAndOrTime 10/13/2023 04:11 PM Actions
5851 WG16 Issues CIM Issues Closed Normal AggregatedRegisteredResoure self association update 08/08/2022 06:01 PM Actions
5850 WG16 Issues CIM Issues Closed Normal RegisteredDistributedResource; Update the PriorityKind description to remove use case specifics. 08/08/2022 06:01 PM Actions
5849 WG16 Issues CIM Issues Closed Normal Association between AggregateNode and Pnode 08/08/2022 06:00 PM Actions
5848 WG16 Issues CIM Issues Closed Normal Association between SchedulingCoordinator and SchedulingCoordiantorUser 08/08/2022 06:00 PM Actions
5846 WG16 Issues CIM Issues Closed Normal ResourcePerformanceGlobalFactor rename 08/08/2022 05:59 PM Actions
5845 WG16 Issues CIM Issues Closed Normal Propose Flexible Ramping Up (FRU or RampUp) and Flexible Ramping Down (FRD or RampDown). Update descriptions of all enum values. 08/08/2022 05:59 PM Actions
5844 WG16 Issues CIM Issues Closed Normal MarketProductType; Propose to remove previously requested Energy Up (ENU) and Energy Down (END). 08/08/2022 05:58 PM Actions
5843 WG16 Issues CIM Issues Closed Normal MarketProduct.rampInterval; Propose to change the datatype of the rampInterval attribute from Float to Minutes. Propose update to description of attribute. 08/08/2022 05:58 PM Actions
5842 WG16 Issues CIM Issues Closed Normal RespourceTimeSeries; Propose to change the cardinality on the association to ResourcePerformanceEvaluation from 1 to 0..many on the ResourcePerformaceEvaluation end. 08/08/2022 05:57 PM Actions
5841 WG16 Issues CIM Issues Closed Normal ResourceTimeSeries; Propose to add an association to RegisteredResource. 08/08/2022 05:57 PM Actions
5840 WG16 Issues CIM Issues Closed Normal ResourcePerformanceEvaluation; Propose to add an association to RegisteredResource. 08/08/2022 05:57 PM Actions
5838 WG16 Issues CIM Issues Closed Normal AutomaticDispInstTypeCommitment rename DR_xxx types to remove DR_ 08/08/2022 05:56 PM Actions
5837 WG16 Issues CIM Issues Closed Normal New class ContractResourceCertificationAgreement 08/08/2022 05:56 PM Actions
5836 WG16 Issues CIM Issues Closed Normal Instructions.instructionStartTime update description 08/08/2022 05:55 PM Actions
(1-100/1448) Per page: 25, 50, 100