Support #465
In a SCD there were LNodes in the substation section that were not associated to a specific IED/LN instance. In particular, an S
Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Solved / Missunderstanding
Start date:
Due date:
% Done:
0%
Estimated time:
ID:
22 (1)
Source:
IOP_2013
TF Unique ID:
22 (1) # IOP_2013
WG10 Proposal:
Tissue 1365
Estimated Completion:
Discuss in Upcoming Meeting:
To discuss in WG10:
Short Proposal:
Improvment of the schema or clarify the part 6. "null" is not a valid value. It should validate against IED names or "None". Also IED names in the IED section shall not be "None".
Standard(s):
Needs More Information:
Assigned TF:
Description
In a SCD there were LNodes in the substation section that were not associated to a specific IED/LN instance. In particular, an SCD file contained an IEDName whose value was “null”.
This file did not import into certain tooling.