Project

General

Profile

Support #516

Buffered reporting testing – anomaly with resynch (write of entryId failed, but buffered reports still sent). Because of indexe

Added by Herbert Falk about 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
-
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
32
Source:
IOP_2015
TF Unique ID:
32 # IOP_2015
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
To discuss in WG10:
Short Proposal:
Standard(s):
Needs More Information:
Assigned TF:

Description

Buffered reporting testing – anomaly with resynch (write of entryId failed, but buffered reports still sent). Because of indexed report control block names, client selected different BRCB on second connection, but had entryId’s from the first. Check reporting guidelines document to make sure entryIds are associated with BRCB instance, not dataset.

#1

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Status changed from New to Closed

Confirm to IEC 61850-6 editor that this issue has been accounted for.

Also available in: Atom PDF