Project

General

Profile

Support #413

Substation part in SCL is mostly non existing in manufacturers scd export files and in form that is defined as in Standard. Subs

Added by Herbert Falk about 3 years ago. Updated about 3 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Standard clarification required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
6
Source:
ENTSO-E
TF Unique ID:
6 # ENTSO-E
WG10 Proposal:

This needs to be harmonised in the standard.

The minimum production of the substation section to be discussed further, (which detail in this section) creation of a new issue.

Closed because it is done

Estimated Completion:
Ed 2.1 FDIS of part 6 in order to be mandatory
Discuss in Upcoming Meeting:
To discuss in WG10:
Short Proposal:

According to IEC 61850-6, it is intended that the substation section is mandatory for an SCD file. But the SICS for System Tools say that the production of a substation section is optional.

Standard(s):
Needs More Information:
Assigned TF:

Description

Substation part in SCL is mostly non existing in manufacturers scd export files and in form that is defined as in Standard. Substation part in ‘configured’ SCLs should not be optional as this is the only way to link certain function to a part of substation Manufacturers tool for this feature.

#1

Updated by Herbert Falk about 3 years ago

  • Status changed from New to Closed

Also available in: Atom PDF