# Project Tracker ID Source Status Priority Standard(s) Subject Updated
509 IEC 61850 User Feedback Task Force Support 24 IOP_2015 Closed Normal

IEC 61850-7-2

1. Report Control Block is disabled and four events (four reports) are generated2. Client sends MMS Write RptEna=true to the BR 06/21/2022 09:12 AM Actions
508 IEC 61850 User Feedback Task Force Support 23 IOP_2015 Closed Normal

IEC 61850-7-2

RptID attribute of a ReportControl section in SCL is optional, as stated in IEC 61850-6. IEC 61850-8-1 states to send RCB objec 06/21/2022 09:12 AM Actions
506 IEC 61850 User Feedback Task Force Support 21 IOP_2015 Closed Normal

6

Issue 1: Content of CID with GOOSE Subscriptions During testing we noticed some CID files contained a single IED, whereas others 06/21/2022 09:12 AM Actions
505 IEC 61850 User Feedback Task Force Support 20 IOP_2015 Closed Normal

6

Statement: an SCT A export an SED file with engineering rights “fix” and expectation was SCT B could add Goose clients after imp 06/21/2022 09:12 AM Actions
504 IEC 61850 User Feedback Task Force Support 19 IOP_2015 Closed Normal

6

When IID file from ICT includes “mustUnderstand” attribute in <GSEcontrol> such as <GSEControl desc="System Logical Device GOOS 06/21/2022 09:12 AM Actions
503 IEC 61850 User Feedback Task Force Support 18 IOP_2015 Closed Normal

6

Issue 1: History section is present in ICD but during import SCT is discarding this history section. Also, maintenance of histor 06/21/2022 09:12 AM Actions
502 IEC 61850 User Feedback Task Force Support 17 IOP_2015 Closed Normal

6

Issue 1: During import of SSD file SST/SCT is not able to recognize Busbar connection node. It is connectivity node and there i 06/21/2022 09:12 AM Actions
501 IEC 61850 User Feedback Task Force Support 16 IOP_2015 Closed Normal

6

PAUL MYRDA: In SCL it is possible to define unbuffered report control blocks with indexed set to false but with max instances se 06/21/2022 09:12 AM Actions
500 IEC 61850 User Feedback Task Force Support 15 IOP_2015 Closed Normal

6

2.2. BufMod is optional for ReportControl. No default value provided by the schema. SCT is interpreting as unbuffered only. Com 06/21/2022 09:12 AM Actions
499 IEC 61850 User Feedback Task Force Support 14 IOP_2015 Closed Normal

6

Issue 4 – Private section – namespace moved from SCL node to Private nodes ICT added the namespace within the privates instead o 06/21/2022 09:12 AM Actions
498 IEC 61850 User Feedback Task Force Support 13 IOP_2015 Closed Normal

6

Issue 3 – GoCB confRev - behaviour if ConfRev=“0“ IED rejected that value. 7-2: If there are inconsistent attribute values in t 06/21/2022 09:12 AM Actions
497 IEC 61850 User Feedback Task Force Support 12 IOP_2015 Closed Normal

6

Issue 2 - IED restrictions not known by SCT 2.1 IED support 50% URCB and 50% BRCB Service section provide a total RCB number 2. 06/21/2022 09:12 AM Actions
496 IEC 61850 User Feedback Task Force Support 11 IOP_2015 Closed Normal

6

DUSTIN: Issue 3: Symmetrical Bindings of DA In case of late Binding at DO/DA Level. IED expects DO at later binding, but source 06/21/2022 09:12 AM Actions
495 IEC 61850 User Feedback Task Force Support 10 IOP_2015 Closed Normal

6

Issue 2: SCT Behavior When Revising/Replacing IED Configuration Between SCT Tools In terms of the data model structure and comm 06/21/2022 09:12 AM Actions
494 IEC 61850 User Feedback Task Force Support 9 IOP_2015 Closed Normal

6

DUSTIN: Issue 1: X/Y Coordinates Upon exchanging the SCD file between SCT tools, the drawing/visualization of the single line d 06/21/2022 09:12 AM Actions
493 IEC 61850 User Feedback Task Force Support 8 IOP_2015 Closed Normal

6

An icd/iid file is not required to include the “original SCL” element. Is it required to be added to the IED instance in the SCD 06/21/2022 09:12 AM Actions
492 IEC 61850 User Feedback Task Force Support 7 IOP_2015 Closed Normal

6

(a) If a device does not support configuration of the ctlModel for a specific DO – what is the correct way to declare this? • De 06/21/2022 09:12 AM Actions
491 IEC 61850 User Feedback Task Force Support 6 IOP_2015 Closed Normal

6

Declaration of CtlModel for controllable CDCs (a) If a device does not support configuration of the ctlModel for a specific DO – 06/21/2022 09:11 AM Actions
490 IEC 61850 User Feedback Task Force Support 5 IOP_2015 Closed Normal

6

In the service section, an IED can declare “modify dataset” to be FALSE. That means, datasets in the IED cannot be changed by th 06/21/2022 09:11 AM Actions
489 IEC 61850 User Feedback Task Force Support 4 IOP_2015 Closed Normal

6

Declaration of Clients in an SCL file: The icd/iid file of a client only device can have a LN at the level of the access point. 06/21/2022 09:11 AM Actions
488 IEC 61850 User Feedback Task Force Support 3 IOP_2015 Closed Normal

6

An ICD file has predefined ReportControlBlock. With the SCT we attached a dataset to one URCB. Afterwards we decide to de-config 06/21/2022 09:11 AM Actions
487 IEC 61850 User Feedback Task Force Support 2 IOP_2015 Closed Normal

6

In the service section, there is the new element “client services”. That element includes GOOSE (default FALSE). Is it required 06/21/2022 09:11 AM Actions
486 IEC 61850 User Feedback Task Force Support 1 IOP_2015 Closed Normal

7-1, 7-4

An ICT has required LGOS configuration coming from SCT to be able to subscribe GOOSE. Is it the way it should work? And is it re 06/21/2022 09:11 AM Actions
507 IEC 61850 User Feedback Task Force Support 22 IOP_2015 Closed Normal If the client reads a SCD file and loads then the data model (or vice versa ???) what data shall a client compare? confRef’s, da 06/21/2022 09:10 AM Actions
513 IEC 61850 User Feedback Task Force Support 28 IOP_2015 Closed Normal

90-4

HSR and PRP are redundancy protocols. In order to prevent a single point of failure, many people are considering 2 red boxes 06/21/2022 09:09 AM Actions
456 IEC 61850 User Feedback Task Force Support 13 IOP_2013 Closed Normal A client only ICD did not have a ClientServices section. An SCT imported the file and assigned used the IED to reserve a RCB wit 06/21/2022 09:00 AM Actions
485 IEC 61850 User Feedback Task Force Support 41 IOP_2013 Closed Normal Some switches discard the IEEE 802.1Q tag known as VLAN 0 on packets sent/received on the trunk ports. Others discard the packet 06/21/2022 09:00 AM Actions
484 IEC 61850 User Feedback Task Force Support 40 IOP_2013 Closed Normal A question was raised in regards can Report EntryIDs be reused after IED restart. If so, guidance needs to be given for system d 06/21/2022 09:00 AM Actions
483 IEC 61850 User Feedback Task Force Support 39 IOP_2013 Closed Normal A question was raised in regards to the expected behavior of a server/BRCB that has been purged (e.g. no events buffered) and th 06/21/2022 09:00 AM Actions
482 IEC 61850 User Feedback Task Force Support 38 IOP_2013 Closed Normal When should buffering start for a reserved and fully configured BRCB. The discussion was that buffering should probably begin up 06/21/2022 09:00 AM Actions
481 IEC 61850 User Feedback Task Force Support 37 IOP_2013 Closed Normal A question was raised in regards to how a client should resynchronize to receive the last report (Buffered Reporting). The sta 06/21/2022 09:00 AM Actions
480 IEC 61850 User Feedback Task Force Support 36 IOP_2013 Closed Normal A different client made use of a URCB that had been reserved in SCL for use by a different client via ClientLN. Currently, there 06/21/2022 09:00 AM Actions
479 IEC 61850 User Feedback Task Force Support 35 IOP_2013 Closed Normal An SCL file was produced that had a GOOSE DataSet that contained members that had FC=CO and FC=CF. The SCT performing the import 06/21/2022 09:00 AM Actions
478 IEC 61850 User Feedback Task Force Support 34 IOP_2013 Closed Normal There is currently no mechanism to allow an array member to be added as a DataSet member In the conformance tables of 8-1, alter 06/21/2022 09:00 AM Actions
477 IEC 61850 User Feedback Task Force Support 33 IOP_2013 Closed Normal Throughout the IOP, there was discussion about validation. However, validation has several different levels to it. There is no v 06/21/2022 09:00 AM Actions
476 IEC 61850 User Feedback Task Force Support 32 IOP_2013 Closed Normal Currently, in SCL, the size of an array is numeric. This could lead to issues of consistency (e.g. one having 32 array elements 06/21/2022 09:00 AM Actions
475 IEC 61850 User Feedback Task Force Support 31 IOP_2013 Closed Normal With the renaming of LNTypes, DOTypes, etc., there should be a specification as to the maximum size for these names. The XSD sho 06/21/2022 09:00 AM Actions
474 IEC 61850 User Feedback Task Force Support 30 IOP_2013 Closed Normal Should all SCTs support a substation section and the ability to associate LNodes into that section. 06/21/2022 09:00 AM Actions
473 IEC 61850 User Feedback Task Force Support 29 IOP_2013 Closed Normal An SCL file was provided that had a <Val> for an OctetString value. A question was raised as to the correct format for the value 06/21/2022 09:00 AM Actions
472 IEC 61850 User Feedback Task Force Support 28 IOP_2013 Closed Normal An ED.2 SCT would not import an ED.1 SCL file. This needs to be addressed with rules of transformation and the definition of a s 06/21/2022 09:00 AM Actions
471 IEC 61850 User Feedback Task Force Support 27 IOP_2013 Closed Normal How should an SCL file express the initial value of GOCB.Ena and SVCB.Ena. It would appear that the Control Block schema definit 06/21/2022 09:00 AM Actions
470 IEC 61850 User Feedback Task Force Support 26 IOP_2013 Closed Normal An ICT provides an IID/ICD file that defines 4 GOCBs. The SCT imports this file, creates an SCD which has only 1 GOCB. The ICT r 06/21/2022 09:00 AM Actions
469 IEC 61850 User Feedback Task Force Support 25 IOP_2013 Closed Normal The iedType attribute is optional within SCL. However, some SCL tools use this as part of validation. Lack of the attribute/valu 06/21/2022 09:00 AM Actions
468 IEC 61850 User Feedback Task Force Support 24 IOP_2013 Closed Normal The mechanism for defining a GI attribute in a ED.2 RCB does not validate and import into an ED.1 ICT. 06/21/2022 09:00 AM Actions
467 IEC 61850 User Feedback Task Force Support 23 IOP_2013 Closed Normal There are normative ENUM definitions for 7-4. (e.g. Mod) but there is no guidance in regards to naming rules (e.g. Modkind). 06/21/2022 09:00 AM Actions
466 IEC 61850 User Feedback Task Force Support 22 (2) IOP_2013 Closed Normal In a SCD there were LNodes in the substation section that were not associated to a specific IED/LN instance. The question was if 06/21/2022 09:00 AM Actions
465 IEC 61850 User Feedback Task Force Support 22 (1) IOP_2013 Closed Normal In a SCD there were LNodes in the substation section that were not associated to a specific IED/LN instance. In particular, an S 06/21/2022 09:00 AM Actions
464 IEC 61850 User Feedback Task Force Support 21 IOP_2013 Closed Normal There is an issue about differentiation between “fixed” /preconfigured DataSets and those that can be changed in a SCT. Some ICT 06/21/2022 09:00 AM Actions
462 IEC 61850 User Feedback Task Force Support 19 IOP_2013 Closed Normal The use of ExtRef to subscribe to a SV was questioned. There are several different mechanisms that could be used in 61850-6 to s 06/21/2022 09:00 AM Actions
460 IEC 61850 User Feedback Task Force Support 17 IOP_2013 Closed Normal The usage of ClientLN in RptEna is optional. What does this mean. 61850-6 made this option for backward compatibility with ED.1. 06/21/2022 09:00 AM Actions
459 IEC 61850 User Feedback Task Force Bug 16 IOP_2013 Closed High

IEC 61850-6

No mechanism in SCL to indicate if the SCT can define/delete/edit RCBs/ExtRefs 06/21/2022 09:00 AM Actions
556 IEC 61850 User Feedback Task Force Support 3 H30 In Progress Normal

IEC 61850-90-20

Rendundant CT/TT measurements 06/21/2022 02:09 AM Actions
616 Server Issues Closed Normal sCnf10 in Ed2 remove voltagelevel and bay name TEMPLATE 06/14/2022 08:28 AM Actions
1866 IEC 61850 Certificate IEC 61850 Certificate Approved Normal CP-MUP [ABB Switzerland Ltd.] 06/13/2022 03:24 PM Actions
2091 IEC 61850 Certificate IEC 61850 Certificate Approved Normal BHEL-MU Merging Unit [Bharat Heavy Electricals Ltd.] 06/13/2022 03:23 PM Actions
2092 IEC 61850 Certificate IEC 61850 Certificate Approved Normal SAMU-IX [Interoptix Inc.] 06/13/2022 03:23 PM Actions
2093 IEC 61850 Certificate IEC 61850 Certificate Approved Normal CMC850 Test Set [OMICRON Electronics GmbH] 06/13/2022 03:22 PM Actions
2094 IEC 61850 Certificate IEC 61850 Certificate Approved Normal PCS-221 Merging Unit [NR Electric Co., Ltd.] 06/13/2022 03:22 PM Actions
2095 IEC 61850 Certificate IEC 61850 Certificate Approved Normal CMC256plus Test Set [OMICRON Electronics GmbH] 06/13/2022 03:21 PM Actions
2096 IEC 61850 Certificate IEC 61850 Certificate Approved Normal CMC353 Test Set [OMICRON Electronics GmbH] 06/13/2022 03:21 PM Actions
2097 IEC 61850 Certificate IEC 61850 Certificate Approved Normal CMC356 Test Set [OMICRON Electronics GmbH] 06/13/2022 03:20 PM Actions
2098 IEC 61850 Certificate IEC 61850 Certificate Approved Normal YSMU-121540 [YOUSUNG Instrument & Electric Co., Ltd.] 06/13/2022 03:20 PM Actions
2099 IEC 61850 Certificate IEC 61850 Certificate Approved Normal MU Agile AMU [ALSTOM Grid UK LTD] 06/13/2022 03:18 PM Actions
2100 IEC 61850 Certificate IEC 61850 Certificate Approved Normal SO-52v11-MUA [Mikronika] 06/13/2022 03:16 PM Actions
2101 IEC 61850 Certificate IEC 61850 Certificate Approved Normal PRS-7395 Smart Terminal & MU [CYG SUNRI Co., Ltd.] 06/13/2022 03:15 PM Actions
2102 IEC 61850 Certificate IEC 61850 Certificate Approved Normal SIPROTEC 7SC805 Merging Unit [Siemens A.G., IC SG EA] 06/13/2022 03:14 PM Actions
2103 IEC 61850 Certificate IEC 61850 Certificate Approved Normal DRTS 64 Relay Test Set [I.S.A. Istrumentazioni Sistemi Automatici S.r.l.] 06/13/2022 03:14 PM Actions
2436 IEC 61850 Certificate IEC 61850 Certificate Approved Normal Siprotec 7SC805 Merging Unit [Siemens Power Automation Ltd.] 06/13/2022 03:13 PM Actions
2511 IEC 61850 Certificate IEC 61850 Certificate Approved Normal F6150sv [Doble Engineering Company] 06/13/2022 03:12 PM Actions
2535 IEC 61850 Certificate IEC 61850 Certificate Approved Normal CSD-603 [Beijing Sifang Automation Co., Ltd.] 06/13/2022 03:12 PM Actions
2601 IEC 61850 Certificate IEC 61850 Certificate Approved Normal FOCS-LTB420 Fiber optic current sensor [ABB Schweiz AG] 06/13/2022 03:10 PM Actions
2633 IEC 61850 Certificate IEC 61850 Certificate Approved Normal SAM600 Merging Unit [ABB Switzerland Ltd.] 06/13/2022 03:10 PM Actions
2684 IEC 61850 Certificate IEC 61850 Certificate Approved Normal INGEPAC EF PB Merging Unit [Ingeteam Power Technology, S.A.] 06/13/2022 03:09 PM Actions
2747 IEC 61850 Certificate IEC 61850 Certificate Approved Normal FOCS-FST kit (Fiber Optic Current Sensor [ABB Schweiz AG] 06/13/2022 03:08 PM Actions
2793 IEC 61850 Certificate IEC 61850 Certificate Approved Normal XMU800 Merging Unit [GE Grid Solutions] 06/13/2022 03:07 PM Actions
2861 IEC 61850 Certificate IEC 61850 Certificate Approved Normal G5 Digital Fault Recorder [Elspec Engineering Ltd.] 06/13/2022 03:07 PM Actions
2949 IEC 61850 Certificate IEC 61850 Certificate Approved Normal SMRT410 Relay Test System (4U4I) [Megger] 06/13/2022 03:06 PM Actions
2952 IEC 61850 Certificate IEC 61850 Certificate Approved Normal SIPROTEC 5 6MU85 Merging Unit / Bay Unit [Siemens AG] 06/13/2022 03:05 PM Actions
5095 Server Issues Closed Normal sAssN1 is missing detailed test case 06/02/2022 02:49 PM Actions
3013 IEC 61850 Certificate IEC 61850 Certificate Approved Normal PCM600 [ABB Oy] 06/01/2022 11:07 AM Actions
5044 WG13 Issues CIM Issues Open Normal Review circuit class in CIM18 05/09/2022 10:58 AM Actions
5062 WG13 Issues CIM Issues Open Low DC auxiliary equipment support 05/09/2022 10:37 AM Actions
3098 IEC 61850 User Feedback Task Force Improvement 1 WG17 In Progress Normal Need to Change 8-1 to allow multiple DOs to be written 03/29/2022 09:36 AM Actions
451 IEC 61850 User Feedback Task Force Bug 8 IOP_2013 Closed High

IEC 61850-6

ICD file of a client only IED 03/15/2022 09:43 AM Actions
449 IEC 61850 User Feedback Task Force Bug 6 IOP_2013 Closed High

IEC 61850-6

GSE MaxTime and MinTime parameters are optional with no default value 03/15/2022 09:40 AM Actions
4989 WG13 Issues CIM Issues Open Normal Feeder:How to modelize a feeder as a collection of equipme 02/16/2022 10:51 AM Actions
3068 IEC 61850 Certificate IEC 61850 Certificate Approved Normal TOR 300 KC3 510 155 (TOP 300) [Relematika, LLC] 02/15/2022 04:38 PM Actions
5012 WG13 Issues CIM Issues Open Normal Exchange of seasonal limit sets.Functionally this is excha 01/26/2022 10:38 AM Actions
5016 WG13 Issues CIM Issues Open Normal OperationalLimit for BranchGroupNeed a means to apply the 01/26/2022 10:32 AM Actions
5153 Server Issues Closed Normal Backward Compatibility of 61869-9 with 9-2 LE 01/25/2022 08:52 AM Actions
5214 WG14 Part 1 Issues CIM Issues New Normal Customer Installation Management (CIM) rename 01/12/2022 02:44 PM Actions
5213 WG14 Part 1 Issues CIM Issues New Normal Customer Account Management (ACT) not following naming convention 01/12/2022 02:44 PM Actions
5212 WG14 Part 1 Issues CIM Issues New Normal CompatibleUnit association to Conceptual Design Development 01/12/2022 02:44 PM Actions
5211 WG14 Part 1 Issues CIM Issues New Normal Missing structural analysis function 01/12/2022 02:44 PM Actions
5210 WG14 Part 1 Issues CIM Issues New Normal Consider to add Business Actor & Role into the IRM for Ed.4 01/12/2022 02:44 PM Actions
5209 WG14 Part 1 Issues CIM Issues New Normal Outage Management Business Function 01/12/2022 02:44 PM Actions
5208 WG14 Part 1 Issues CIM Issues New Normal To link ArchiMate to UML on how to use IRM for Part teams 01/12/2022 02:44 PM Actions
5207 WG14 Part 1 Issues CIM Issues New Normal Add Business Roles into IRM Model (for Ed.4) 01/12/2022 02:44 PM Actions
5206 WG14 Part 1 Issues CIM Issues New Normal TC57 WG13 / 14 scope 01/12/2022 02:44 PM Actions
5205 WG14 Part 1 Issues CIM Issues New Normal Asset Decision Support (ADS) 01/12/2022 02:44 PM Actions