Support #494

DUSTIN: Issue 1: X/Y Coordinates Upon exchanging the SCD file between SCT tools, the drawing/visualization of the single line d

Added by Herbert Falk over 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
-
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
9
Source:
IOP_2015
TF Unique ID:
9 # IOP_2015
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
To discuss in WG10:
Short Proposal:

Consider with improvement of x/y coordinates.
Explicit busbar would help CIM harmonization.
See TISSUE 1407 => Ed. 3

Standard(s):

6

Needs More Information:
Assigned TF:

Description

DUSTIN:
Issue 1: X/Y Coordinates
Upon exchanging the SCD file between SCT tools, the drawing/visualization of the single line diagram is incorrectly depicted. In general, there are a lack of X,Y coordinates supported to visualize the single line diagram between SCT tools. This is similar to SSD Problem Report (Vladen). Require coordinates for:
- Connectivity nodes
- Size & Location of All Objects
Some users/utilities have already created a standard/schema to model their single line diagram. Suggest using these as a starting point.

VLADAN: During import of SSD file SST/SCT is not able to recognize Busbar connection node.
It is connectivity node and there is no rule to recognize it during import.

#1

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Status changed from New to Closed

Confirm to IEC 61850-6 editor that this issue has been accounted for.