Support #493

An icd/iid file is not required to include the “original SCL” element. Is it required to be added to the IED instance in the SCD

Added by Herbert Falk over 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
-
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
8
Source:
IOP_2015
TF Unique ID:
8 # IOP_2015
WG10 Proposal:

TISSUE 1450

Estimated Completion:
Discuss in Upcoming Meeting:
To discuss in WG10:
Short Proposal:

TISSUE to be posted by xxx, referring to 1398; make it clear that:
- ICD (Ed. 2 or later) shall set originalSclXxx attributes
- SCT shall set originalSclXxx attributes on importing an IxD file without originalSclXxx attributes according to the version of the SCL file
Add rule that for an IxD file, the originalSclXxx values shall match the SCL version/revision/release.

Standard(s):

6

Needs More Information:
Assigned TF:

Description

An icd/iid file is not required to include the “original SCL” element.
Is it required to be added to the IED instance in the SCD file by the SCT in any case or is it sufficient to be added only if different from version referred to in namespace of the SCD?

#1

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Status changed from New to Closed

Confirm to IEC 61850-6 editor that this issue has been accounted for.