Support #490
In the service section, an IED can declare “modify dataset” to be FALSE. That means, datasets in the IED cannot be changed by th
0%
TISSUE 1444
Issue: we may have 9-2 DS which are “fixed”. Introduce modifiable flag on DS level?
TISSUE to be posted by Herb.
6
Description
In the service section, an IED can declare “modify dataset” to be FALSE. That means, datasets in the IED cannot be changed by the system tool.
Assume, an IED supports 10 datasets (declared in the service section), has preconfigured three datasets and declares modify dataset to be FALSE. Does the modify dataset only apply to the three preconfigured ones, and the SCT can add (and configure) 7 new datasets? Or does this mean, that the SCT cannot add any dataset, since it is no allowed to modify datasets.
If the second would be true, how can an IED declare that datasets can be added, but the existing ones cannot be changed?
Probably need more granularity on “modify dataset”
Updated by Carlos Rodriguez del Castillo almost 2 years ago
- Status changed from New to Closed
Confirm to IEC 61850-6 editor that this issue has been accounted for.