Support #509
1. Report Control Block is disabled and four events (four reports) are generated2. Client sends MMS Write RptEna=true to the BR
Status:
Closed
Priority:
Normal
Assignee:
-
Category:
-
Start date:
Due date:
% Done:
0%
Estimated time:
ID:
24
Source:
IOP_2015
TF Unique ID:
24 # IOP_2015
WG10 Proposal:
Including in 2.1 amendment part 7-2 (17.2.2.1)Tissue 1454
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
Standard(s):
IEC 61850-7-2
Needs More Information:
Assigned TF:
Description
1. Report Control Block is disabled and four events (four reports) are generated
2. Client sends MMS Write RptEna=true to the BRCB
3. Server sends the four InformationReport
4. Server sends the MMS Write success to the MMS Write RptEna=true request
5. Client ignores the four InformationReport because they were received before receiving the confirmation of the MMS Write RptEna=true operation
Should the standard clarify that this is a valid situation so the client should accept the InformationReport received before the confirmation to the Write operation?
Updated by Vladan Cvejic almost 2 years ago
- Subject changed from 1. Report Control Block is disabled and four events (four reports) are generated 2. Client sends MMS Write RptEna=true to the BR to 1. Report Control Block is disabled and four events (four reports) are generated2. Client sends MMS Write RptEna=true to the BR
- WG10 Proposal changed from Including in 2.1 amendment part 7-2 (17.2.2.1) Tissue 1454 to Including in 2.1 amendment part 7-2 (17.2.2.1)Tissue 1454
- Discuss in Upcoming Meeting set to No
- To discuss in WG10 set to No
- Standard(s) changed from 2-Jul to IEC 61850-7-2
Updated by Carlos Rodriguez del Castillo almost 2 years ago
- Status changed from New to Closed
Confirm to IEC 61850-6 editor that this issue has been accounted for.