565 IEC 61850 User Feedback Task Force Support 37 ENTSO-E Closed Normal

IEC 61850-7-4/90-3

S/S related applications: DC battery model and converter/charger/rectifier alarms 02/11/2021 07:00 AM Actions
481 IEC 61850 User Feedback Task Force Support 37 IOP_2013 Closed Normal A question was raised in regards to how a client should resynchronize to receive the last report (Buffered Reporting). The sta 06/21/2022 09:00 AM Actions
564 IEC 61850 User Feedback Task Force Support 36 ENTSO-E Closed Normal

IEC 61850-90-6

S/S related applications: Auxiliary transfer 02/11/2021 07:01 AM Actions
480 IEC 61850 User Feedback Task Force Support 36 IOP_2013 Closed Normal A different client made use of a URCB that had been reserved in SCL for use by a different client via ClientLN. Currently, there 06/21/2022 09:00 AM Actions
563 IEC 61850 User Feedback Task Force Support 35 ENTSO-E Closed Normal

IEC 61850-7-4

Transformer diff. protection: Protection blocked by harmonics 02/11/2021 07:01 AM Actions
479 IEC 61850 User Feedback Task Force Support 35 IOP_2013 Closed Normal An SCL file was produced that had a GOOSE DataSet that contained members that had FC=CO and FC=CF. The SCT performing the import 06/21/2022 09:00 AM Actions
562 IEC 61850 User Feedback Task Force Support 34 ENTSO-E Closed Normal

IEC 61850-7-4

Transformer diff. protection: Restricted earthfault protection 02/11/2021 07:02 AM Actions
478 IEC 61850 User Feedback Task Force Support 34 IOP_2013 Closed Normal There is currently no mechanism to allow an array member to be added as a DataSet member In the conformance tables of 8-1, alter 06/21/2022 09:00 AM Actions
518 IEC 61850 User Feedback Task Force Support 34 IOP_2015 Closed Normal Does the SVID character have to be specifically mentioned to be within 10-34 characters? Some of the vendors have implemented th 06/21/2022 09:12 AM Actions
561 IEC 61850 User Feedback Task Force Support 33 ENTSO-E Closed Normal

IEC 61850-7-500

Pole discrepancy: no LN to cover Trip and pole disc 02/11/2021 06:53 AM Actions
477 IEC 61850 User Feedback Task Force Support 33 IOP_2013 Closed Normal Throughout the IOP, there was discussion about validation. However, validation has several different levels to it. There is no v 06/21/2022 09:00 AM Actions
517 IEC 61850 User Feedback Task Force Support 33 IOP_2015 Closed Normal IEC 61850-9-3 slaves can by design lock themselves to IEEE C37.238 (Power Profile) masters. This is intended behavior, since IEC 06/21/2022 09:12 AM Actions
560 IEC 61850 User Feedback Task Force Support 32 ENTSO-E Closed Normal

IEC 61850-7-4

Busbar protection: Simplified logic 02/11/2021 07:02 AM Actions
476 IEC 61850 User Feedback Task Force Support 32 IOP_2013 Closed Normal Currently, in SCL, the size of an array is numeric. This could lead to issues of consistency (e.g. one having 32 array elements 06/21/2022 09:00 AM Actions
516 IEC 61850 User Feedback Task Force Support 32 IOP_2015 Closed Normal Buffered reporting testing – anomaly with resynch (write of entryId failed, but buffered reports still sent). Because of indexe 06/21/2022 09:12 AM Actions
559 IEC 61850 User Feedback Task Force Support 31 ENTSO-E Closed Normal

IEC 61850-7-4

Busbar protection: ARC detection protection 12/06/2022 09:02 AM Actions
475 IEC 61850 User Feedback Task Force Support 31 IOP_2013 Closed Normal With the renaming of LNTypes, DOTypes, etc., there should be a specification as to the maximum size for these names. The XSD sho 06/21/2022 09:00 AM Actions
515 IEC 61850 User Feedback Task Force Support 31 IOP_2015 Closed Normal These test cases assume that a server will send a negative response to an operate to the same value. Some servers will accept th 06/21/2022 09:12 AM Actions
558 IEC 61850 User Feedback Task Force Support 30 ENTSO-E Closed Normal

IEC 61850-7-4

Busbar protection (BBP): Diff/Kirchoff BBP 12/06/2022 09:02 AM Actions
474 IEC 61850 User Feedback Task Force Support 30 IOP_2013 Closed Normal Should all SCTs support a substation section and the ability to associate LNodes into that section. 06/21/2022 09:00 AM Actions
408 IEC 61850 User Feedback Task Force Bug 3.2 ENTSO-E Closed High PICS, MICS and other statements documents are not formally defined 02/09/2021 06:20 AM Actions
407 IEC 61850 User Feedback Task Force Feature 3.1 ENTSO-E Closed Normal "Vendor/User” and “Vendor/Vendor” Interoperability list 02/11/2021 06:17 AM Actions
446 IEC 61850 User Feedback Task Force Bug 3 IOP_2013 Closed High

IEC 61850-6

The actual format required for an ClientLN (used for ReportControl Block reservation) is not specified fully or in an understand 02/11/2021 06:30 AM Actions
488 IEC 61850 User Feedback Task Force Support 3 IOP_2015 Closed Normal

6

An ICD file has predefined ReportControlBlock. With the SCT we attached a dataset to one URCB. Afterwards we decide to de-config 06/21/2022 09:11 AM Actions
522 IEC 61850 User Feedback Task Force Feature 3 IOP_2017/5 Closed Normal

IEC 61850-6

SCD file has “originalSclVersion=2007” for all IED, including Ed1 devices 06/21/2022 09:24 AM Actions
440 IEC 61850 User Feedback Task Force Support 3 Vattenfall Closed Normal The specified sigal has a utility process name independent of used protcol. E.g. "start of distance protection". Also link to a 06/21/2022 09:19 AM Actions
557 IEC 61850 User Feedback Task Force Feature 29 ENTSO-E Closed Normal

IEC 61850-7-4

Lockout functionality: how to model by different protection functions? 02/11/2021 06:05 AM Actions
473 IEC 61850 User Feedback Task Force Support 29 IOP_2013 Closed Normal An SCL file was provided that had a <Val> for an OctetString value. A question was raised as to the correct format for the value 06/21/2022 09:00 AM Actions
514 IEC 61850 User Feedback Task Force Support 29 IOP_2015 Closed Normal Priority of error checking in controls – i.e. position-reached instead of Blocked-by-switching-hierarchy. The order of checks i 06/21/2022 09:12 AM Actions
437 IEC 61850 User Feedback Task Force Support 28 ENTSO-E Closed Normal

IEC 61850-6

SCL: Use of InRef and ExtRef not possible in many tools 02/11/2021 06:57 AM Actions
472 IEC 61850 User Feedback Task Force Support 28 IOP_2013 Closed Normal An ED.2 SCT would not import an ED.1 SCL file. This needs to be addressed with rules of transformation and the definition of a s 06/21/2022 09:00 AM Actions
513 IEC 61850 User Feedback Task Force Support 28 IOP_2015 Closed Normal

90-4

HSR and PRP are redundancy protocols. In order to prevent a single point of failure, many people are considering 2 red boxes 06/21/2022 09:09 AM Actions
436 IEC 61850 User Feedback Task Force Support 27 ENTSO-E Closed Normal Too many options in the standard 06/05/2023 01:59 AM Actions
471 IEC 61850 User Feedback Task Force Support 27 IOP_2013 Closed Normal How should an SCL file express the initial value of GOCB.Ena and SVCB.Ena. It would appear that the Control Block schema definit 06/21/2022 09:00 AM Actions
512 IEC 61850 User Feedback Task Force Support 27 IOP_2015 Closed Normal

90-4

Testing unconfigured VLAN, there is a question of how VLAN tags (e.g. 20) should be handled by the HSR ring. However, what sho 06/21/2022 09:12 AM Actions
546 IEC 61850 User Feedback Task Force Feature 27 IOP_2017/47 Closed Normal

IEC 61850-6 §10 annex G

Different level of expectations between the ICT and SCT 02/11/2021 07:16 AM Actions
435 IEC 61850 User Feedback Task Force Support 26 ENTSO-E Closed Normal Interoperability between vendor products is not verified/certified by UCA 02/11/2021 07:06 AM Actions
470 IEC 61850 User Feedback Task Force Support 26 IOP_2013 Closed Normal An ICT provides an IID/ICD file that defines 4 GOCBs. The SCT imports this file, creates an SCD which has only 1 GOCB. The ICT r 06/21/2022 09:00 AM Actions
511 IEC 61850 User Feedback Task Force Support 26 IOP_2015 Closed Normal

2-Sep

The Quality bits alignment in 9-2LE seems different from 8-1 quality bits with ASN.1. So it caused confusion that which bit shou 06/21/2022 09:12 AM Actions
545 IEC 61850 User Feedback Task Force Feature 26 IOP_2017/46 Closed Normal

IEC 61850-6-2

SLD visualization issues in SCL 06/21/2022 09:24 AM Actions
434 IEC 61850 User Feedback Task Force Support 25 ENTSO-E Closed Normal Freedom of choice what IEC 61850 services are to be tested seem too open. The vendor can select exactly what UCA accredited test 12/06/2022 09:01 AM Actions
469 IEC 61850 User Feedback Task Force Support 25 IOP_2013 Closed Normal The iedType attribute is optional within SCL. However, some SCL tools use this as part of validation. Lack of the attribute/valu 06/21/2022 09:00 AM Actions
510 IEC 61850 User Feedback Task Force Support 25 IOP_2015 Closed Normal

IEC 61850-7-4

For the latest TISSUE 1361 for Ed2.0 (statement in the attachment), there are two things to be clarified:1. The statement: Swit 06/21/2022 09:12 AM Actions
544 IEC 61850 User Feedback Task Force Feature 25 IOP_2017/44 Closed Normal

IEC 61850-7-5

TestBlock condition implemented only in XCBR and not in any of Rxxx and Pxxx logical node 02/11/2021 07:19 AM Actions
433 IEC 61850 User Feedback Task Force Support 24 ENTSO-E Closed Normal

IEC 61850-10

Client implementation Level A certification 02/11/2021 07:08 AM Actions
468 IEC 61850 User Feedback Task Force Support 24 IOP_2013 Closed Normal The mechanism for defining a GI attribute in a ED.2 RCB does not validate and import into an ED.1 ICT. 06/21/2022 09:00 AM Actions
509 IEC 61850 User Feedback Task Force Support 24 IOP_2015 Closed Normal

IEC 61850-7-2

1. Report Control Block is disabled and four events (four reports) are generated2. Client sends MMS Write RptEna=true to the BR 06/21/2022 09:12 AM Actions
543 IEC 61850 User Feedback Task Force Feature 24 IOP_2017/40 Closed Normal

IEC 61850-8-1

Operability issues between vendors that prevent R-SV testing between substations 02/11/2021 07:20 AM Actions
432 IEC 61850 User Feedback Task Force Support 23 ENTSO-E Closed Normal There are interoperability problems between client and server IEDs due to product implementation. 02/11/2021 07:33 AM Actions
467 IEC 61850 User Feedback Task Force Support 23 IOP_2013 Closed Normal There are normative ENUM definitions for 7-4. (e.g. Mod) but there is no guidance in regards to naming rules (e.g. Modkind). 06/21/2022 09:00 AM Actions