Feature #522

SCD file has “originalSclVersion=2007” for all IED, including Ed1 devices

Added by Herbert Falk over 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Standard extension required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
3
Source:
IOP_2017/5
TF Unique ID:
3 # IOP_2017/5
WG10 Proposal:

clarification needed in table 10 regarding originalSclVersion default value.Update below table 10 to force SCT to fill them -> OK

Estimated Completion:
Solved in IEC 61850-6 Ed 2.1
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:

Edition 2.1 line 2509-2510 (of INF) states: “Both attributes are set by the IED tool when creating the ICD or IID file, and shall be kept within an SCD file.”No issue for the standard.

Standard(s):

IEC 61850-6

Needs More Information:
Assigned TF:

Description

SCD file has “originalSclVersion=2007” for all IED, including First Edition devices.

SCT should have added “2003” when originalSclVersion/OriginalSclRevision was not in ICD file.

#1

Updated by Vladan Cvejic about 3 years ago

  • Subject changed from SCD file has “originalSclVersion=2007” for all IED, including First Edition devices. SCT should have added “2003” when original to SCD file has “originalSclVersion=2007” for all IED, including Ed1 devices
  • Status changed from New to In Progress
  • Short Proposal changed from Edition 2.1 line 2509-2510 (of INF) states: “Both attributes are set by the IED tool when creating the ICD or IID file, and shall be kept within an SCD file.” No issue for the standard. to Edition 2.1 line 2509-2510 (of INF) states: “Both attributes are set by the IED tool when creating the ICD or IID file, and shall be kept within an SCD file.”No issue for the standard.
  • Standard(s) changed from 6 to IEC 61850-6
  • WG10 Proposal changed from clarification needed in table 10 regarding originalSclVersion default value. Update below table 10 to force SCT to fill them -> OK to clarification needed in table 10 regarding originalSclVersion default value.Update below table 10 to force SCT to fill them -> OK
  • Discuss in Upcoming Meeting set to No

Checking done.

#2

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Status changed from In Progress to Closed

Confirm to IEC 61850-6 editor that this issue has been accounted for.