# Project Tracker ID Source Status Priority Standard(s) Subject Updated
535 IEC 61850 User Feedback Task Force Support 16 IOP_2017/25 Closed Normal

6

SCD file removed unconfigured GOOSE control block but did not remove the Connected AP section contained GSE information. 06/21/2022 09:13 AM Actions
506 IEC 61850 User Feedback Task Force Support 21 IOP_2015 Closed Normal

6

Issue 1: Content of CID with GOOSE Subscriptions During testing we noticed some CID files contained a single IED, whereas others 06/21/2022 09:12 AM Actions
505 IEC 61850 User Feedback Task Force Support 20 IOP_2015 Closed Normal

6

Statement: an SCT A export an SED file with engineering rights “fix” and expectation was SCT B could add Goose clients after imp 06/21/2022 09:12 AM Actions
504 IEC 61850 User Feedback Task Force Support 19 IOP_2015 Closed Normal

6

When IID file from ICT includes “mustUnderstand” attribute in <GSEcontrol> such as <GSEControl desc="System Logical Device GOOS 06/21/2022 09:12 AM Actions
503 IEC 61850 User Feedback Task Force Support 18 IOP_2015 Closed Normal

6

Issue 1: History section is present in ICD but during import SCT is discarding this history section. Also, maintenance of histor 06/21/2022 09:12 AM Actions
502 IEC 61850 User Feedback Task Force Support 17 IOP_2015 Closed Normal

6

Issue 1: During import of SSD file SST/SCT is not able to recognize Busbar connection node. It is connectivity node and there i 06/21/2022 09:12 AM Actions
501 IEC 61850 User Feedback Task Force Support 16 IOP_2015 Closed Normal

6

PAUL MYRDA: In SCL it is possible to define unbuffered report control blocks with indexed set to false but with max instances se 06/21/2022 09:12 AM Actions
500 IEC 61850 User Feedback Task Force Support 15 IOP_2015 Closed Normal

6

2.2. BufMod is optional for ReportControl. No default value provided by the schema. SCT is interpreting as unbuffered only. Com 06/21/2022 09:12 AM Actions
499 IEC 61850 User Feedback Task Force Support 14 IOP_2015 Closed Normal

6

Issue 4 – Private section – namespace moved from SCL node to Private nodes ICT added the namespace within the privates instead o 06/21/2022 09:12 AM Actions
498 IEC 61850 User Feedback Task Force Support 13 IOP_2015 Closed Normal

6

Issue 3 – GoCB confRev - behaviour if ConfRev=“0“ IED rejected that value. 7-2: If there are inconsistent attribute values in t 06/21/2022 09:12 AM Actions
497 IEC 61850 User Feedback Task Force Support 12 IOP_2015 Closed Normal

6

Issue 2 - IED restrictions not known by SCT 2.1 IED support 50% URCB and 50% BRCB Service section provide a total RCB number 2. 06/21/2022 09:12 AM Actions
496 IEC 61850 User Feedback Task Force Support 11 IOP_2015 Closed Normal

6

DUSTIN: Issue 3: Symmetrical Bindings of DA In case of late Binding at DO/DA Level. IED expects DO at later binding, but source 06/21/2022 09:12 AM Actions
495 IEC 61850 User Feedback Task Force Support 10 IOP_2015 Closed Normal

6

Issue 2: SCT Behavior When Revising/Replacing IED Configuration Between SCT Tools In terms of the data model structure and comm 06/21/2022 09:12 AM Actions
494 IEC 61850 User Feedback Task Force Support 9 IOP_2015 Closed Normal

6

DUSTIN: Issue 1: X/Y Coordinates Upon exchanging the SCD file between SCT tools, the drawing/visualization of the single line d 06/21/2022 09:12 AM Actions
493 IEC 61850 User Feedback Task Force Support 8 IOP_2015 Closed Normal

6

An icd/iid file is not required to include the “original SCL” element. Is it required to be added to the IED instance in the SCD 06/21/2022 09:12 AM Actions
492 IEC 61850 User Feedback Task Force Support 7 IOP_2015 Closed Normal

6

(a) If a device does not support configuration of the ctlModel for a specific DO – what is the correct way to declare this? • De 06/21/2022 09:12 AM Actions
491 IEC 61850 User Feedback Task Force Support 6 IOP_2015 Closed Normal

6

Declaration of CtlModel for controllable CDCs (a) If a device does not support configuration of the ctlModel for a specific DO – 06/21/2022 09:11 AM Actions
490 IEC 61850 User Feedback Task Force Support 5 IOP_2015 Closed Normal

6

In the service section, an IED can declare “modify dataset” to be FALSE. That means, datasets in the IED cannot be changed by th 06/21/2022 09:11 AM Actions
489 IEC 61850 User Feedback Task Force Support 4 IOP_2015 Closed Normal

6

Declaration of Clients in an SCL file: The icd/iid file of a client only device can have a LN at the level of the access point. 06/21/2022 09:11 AM Actions
488 IEC 61850 User Feedback Task Force Support 3 IOP_2015 Closed Normal

6

An ICD file has predefined ReportControlBlock. With the SCT we attached a dataset to one URCB. Afterwards we decide to de-config 06/21/2022 09:11 AM Actions
487 IEC 61850 User Feedback Task Force Support 2 IOP_2015 Closed Normal

6

In the service section, there is the new element “client services”. That element includes GOOSE (default FALSE). Is it required 06/21/2022 09:11 AM Actions
511 IEC 61850 User Feedback Task Force Support 26 IOP_2015 Closed Normal

2-Sep

The Quality bits alignment in 9-2LE seems different from 8-1 quality bits with ASN.1. So it caused confusion that which bit shou 06/21/2022 09:12 AM Actions
524 IEC 61850 User Feedback Task Force Support 5 IOP_2017/7 Closed Normal

1-Aug

The use of the Simulation bit in the R-GOOSE Payload is not clearly defined. It refers only to 8-1 which currently only specifie 06/21/2022 09:13 AM Actions
5011 WG13 Issues CIM Issues Closed High The 61970 452 profile and 456 profile both contain the same 10/20/2023 10:13 AM Actions
4926 WG13 Issues CIM Issues Closed High TapChangerKind and TransformerControlMode should be dropped 10/20/2023 10:12 AM Actions
4918 WG13 Issues CIM Issues Closed High EnergySource attributes rn and xn should be named r2 and x2 10/20/2023 09:56 AM Actions
4915 WG13 Issues CIM Issues Closed High The LoadResponseCharacteristic is different for steady stat 04/12/2023 09:48 AM Actions
4917 WG13 Issues CIM Issues Closed High Documenation of LoadResponseCharacteristic exponents Sugg 02/19/2023 02:38 AM Actions
5004 WG13 Issues CIM Issues Closed High Short circuit data for power electronicsCurrently PowerEle 02/11/2023 01:24 AM Actions
5006 WG13 Issues CIM Issues Closed High Overlap between transformer xMin and xThe TransformerEnd.x 02/07/2023 01:37 AM Actions
5045 WG13 Issues CIM Issues Closed High Voltage-dependent reactive capability curve support 02/07/2023 01:24 AM Actions
403 IEC 61850 User Feedback Task Force Bug 1 ENTSO-E Closed High Problem exchanging SCL file between tools 02/09/2021 06:22 AM Actions
408 IEC 61850 User Feedback Task Force Bug 3.2 ENTSO-E Closed High PICS, MICS and other statements documents are not formally defined 02/09/2021 06:20 AM Actions
410 IEC 61850 User Feedback Task Force Bug 4.2 ENTSO-E Closed High Data models using GGIO when not needed 02/09/2021 06:19 AM Actions
444 IEC 61850 User Feedback Task Force Bug 1 IOP_2013 Closed High Mixing ed1 and ed2 data models in an ed2 SCL file. 02/09/2021 06:18 AM Actions
454 IEC 61850 User Feedback Task Force Bug 11 IOP_2013 Closed High Data model: extension of logical nodes with new DOs. Question about namespace. 02/09/2021 06:16 AM Actions
406 IEC 61850 User Feedback Task Force Bug 2.3 ENTSO-E Closed High Configuration of datasets by users 02/03/2021 03:55 PM Actions
6756 General Testing Issues Improvement Closed Normal Should UCA accredit and Certify IEC 61850-3 04/16/2024 08:50 AM Actions
6674 Server Issues Closed Normal Discuss changes to submission form and Certificates 03/01/2024 10:10 AM Actions
5910 Server Issues Closed Normal Need to test that IEDs support 1 Step and 2 Step clocks: IOP 2022 03/01/2024 09:53 AM Actions
4916 WG13 Issues CIM Issues Closed Normal documenation on VoltagteControlZone is wrong. This may hav 02/04/2024 02:04 AM Actions
5049 WG13 Issues CIM Issues Closed Normal Inconsistent naming for p,q,r,x and others 02/04/2024 01:58 AM Actions
4806 WG13 Issues CIM Issues Closed Normal ERCOT angle difference limit setAngleDifferenceLimitSet - 10/20/2023 09:56 AM Actions
5306 WG14 Part 1 Issues CIM Issues Closed Normal test issue 10/14/2023 09:59 AM Actions
5795 WG16 Issues CIM Issues Closed Normal ResourceTimeSeriesFactor add attributes value1Description and value2Description 10/13/2023 04:14 PM Actions
5799 WG16 Issues CIM Issues Closed Normal Add marketEvaluationPointType attribute (String) to the MarketEvaluationPoint class 10/13/2023 04:14 PM Actions
5800 WG16 Issues CIM Issues Closed Normal Add meteringMethod attribute (String) in the MarketEvaluationPoint class 10/13/2023 04:14 PM Actions
5801 WG16 Issues CIM Issues Closed Normal Add settlementMethod attribute (String) in the MarketEvaluationPoint class 10/13/2023 04:13 PM Actions
5804 WG16 Issues CIM Issues Closed Normal Add meteredDataCollectionMethod attribute (String) in the MarketEvaluationPoint class 10/13/2023 04:13 PM Actions
5805 WG16 Issues CIM Issues Closed Normal Add gridAgreementType attribute (String) in the MarketEvaluationPoint class 10/13/2023 04:13 PM Actions
(101-150/1448) Per page: 25, 50, 100