# Project Tracker ID Source Status Priority Standard(s) Subject Updated
592 IEC 61850 User Feedback Task Force Feature IntApp IOP_2019 Closed Normal Invalid SCL file due to wrong allocation fo GoCBs 06/21/2022 09:29 AM Actions
417 IEC 61850 User Feedback Task Force Support 9 ENTSO-E Closed Normal

6-100

There is no mechanism proposed by the Standard to positively identify data points in the data model. For instance PTOC can refer 12/06/2022 09:01 AM Actions
528 IEC 61850 User Feedback Task Force Feature 9 IOP_2017/15 Closed Normal

IEC 61850-6

SCD files have type defined where bType does not equal Enum or Struct, which does not follow the IEC 61850-6 description 06/21/2022 09:24 AM Actions
494 IEC 61850 User Feedback Task Force Support 9 IOP_2015 Closed Normal

6

DUSTIN: Issue 1: X/Y Coordinates Upon exchanging the SCD file between SCT tools, the drawing/visualization of the single line d 06/21/2022 09:12 AM Actions
452 IEC 61850 User Feedback Task Force Feature 9 IOP_2013 Closed Normal

IEC 61850-6

What is the meaning of RptEna max=0? 02/11/2021 07:48 AM Actions
451 IEC 61850 User Feedback Task Force Bug 8 IOP_2013 Closed High

IEC 61850-6

ICD file of a client only IED 03/15/2022 09:43 AM Actions
527 IEC 61850 User Feedback Task Force Support 8 IOP_2017/10 Closed Normal Regarding the Network infrastructure: Some MU/SAMU cannot configure their SV stream to different VLAN ID , fixed to 0 (but can c 06/21/2022 09:13 AM Actions
493 IEC 61850 User Feedback Task Force Support 8 IOP_2015 Closed Normal

6

An icd/iid file is not required to include the “original SCL” element. Is it required to be added to the IED instance in the SCD 06/21/2022 09:12 AM Actions
416 IEC 61850 User Feedback Task Force Support 8 ENTSO-E Closed Normal

IEC 61850-6

Implementation and integration software of different manufacturers should have same mandatory tasks in order to be used as tools 02/11/2021 08:00 AM Actions
415 IEC 61850 User Feedback Task Force Support 7.1 ENTSO-E Closed Normal

IEC 61850-7-2

Standard is written in general opinion that Ethernet is fully capable to carry all its tasks 02/11/2021 08:01 AM Actions
450 IEC 61850 User Feedback Task Force Bug 7 IOP_2013 Closed High

IEC 61850-6

SCL namespace "2007A" not accepting LDNs as "2007" 06/05/2023 01:59 AM Actions
526 IEC 61850 User Feedback Task Force Feature 7 IOP_2017/9 Closed Normal

IEC 61850-6

Definition of a data set must contain a data object name but SCL does not require the doName attribute in the <FCDA/> element 06/21/2022 09:24 AM Actions
492 IEC 61850 User Feedback Task Force Support 7 IOP_2015 Closed Normal

6

(a) If a device does not support configuration of the ctlModel for a specific DO – what is the correct way to declare this? • De 06/21/2022 09:12 AM Actions
601 IEC 61850 User Feedback Task Force Feature 637 IOP_2019 Closed Normal

IEC 61850-90-16

ICD files with empty type=”” attribute in their IED element 06/21/2022 09:29 AM Actions
414 IEC 61850 User Feedback Task Force Support 6.2 ENTSO-E Closed Normal SCD from system integrator not containing comprehensive substation section 02/03/2021 02:42 PM Actions
449 IEC 61850 User Feedback Task Force Bug 6 IOP_2013 Closed High

IEC 61850-6

GSE MaxTime and MinTime parameters are optional with no default value 03/15/2022 09:40 AM Actions
525 IEC 61850 User Feedback Task Force Support 6 IOP_2017/8 Resolved Normal

IEC 61850-6

IEC 61850-6 does not allow the authentication configuration (none, password, weak, strong or certificate) to be used for Client 05/09/2023 09:32 AM Actions
491 IEC 61850 User Feedback Task Force Support 6 IOP_2015 Closed Normal

6

Declaration of CtlModel for controllable CDCs (a) If a device does not support configuration of the ctlModel for a specific DO – 06/21/2022 09:11 AM Actions
443 IEC 61850 User Feedback Task Force Feature 6 Vattenfall Closed Normal

IEC 61850-7-1

Requirement for guideline - generic interfacing logical nodes are used for outputs and inputs ( destroys the semantic meaning of signals) 02/11/2021 07:58 AM Actions
413 IEC 61850 User Feedback Task Force Support 6 ENTSO-E Closed Normal Substation part in SCL is mostly non existing in manufacturers scd export files and in form that is defined as in Standard. Subs 02/03/2021 02:42 PM Actions
583 IEC 61850 User Feedback Task Force Support 55 ENTSO-E Closed Normal

IEC 61850-7-4

Autoreclosure: Autoreclosure - 3ph closing command missing 12/06/2022 09:38 AM Actions
582 IEC 61850 User Feedback Task Force Support 54 ENTSO-E Closed Normal

IEC 61850-7-4, 7-5

Synchrocheck: Synchrocheck - missing signals 12/06/2022 09:37 AM Actions
581 IEC 61850 User Feedback Task Force Support 53 ENTSO-E Closed Normal

IEC 61850-7-4, 7-5

S/S related applications: Disturbance recorder - communication session active 12/06/2022 09:37 AM Actions
580 IEC 61850 User Feedback Task Force Support 52 ENTSO-E Resolved Normal

IEC 61850-7-500

Voltage protection: Undervoltage protection - 3ph operate 05/09/2023 09:32 AM Actions
579 IEC 61850 User Feedback Task Force Support 51 ENTSO-E Resolved Normal

IEC 61850-7-500

Voltage protection: Overvoltage protection - 3ph operate 05/09/2023 09:32 AM Actions
578 IEC 61850 User Feedback Task Force Feature 50 ENTSO-E Closed Normal

IEC 61850-7-4

Busbar protection: End Fault protection - model definition required. 12/06/2022 09:37 AM Actions
442 IEC 61850 User Feedback Task Force Bug 5 Vattenfall Closed High

IEC 61850-90-30

Maping LNode (substation section) to LN (IED section) 12/05/2023 08:30 AM Actions
524 IEC 61850 User Feedback Task Force Support 5 IOP_2017/7 Closed Normal

1-Aug

The use of the Simulation bit in the R-GOOSE Payload is not clearly defined. It refers only to 8-1 which currently only specifie 06/21/2022 09:13 AM Actions
490 IEC 61850 User Feedback Task Force Support 5 IOP_2015 Closed Normal

6

In the service section, an IED can declare “modify dataset” to be FALSE. That means, datasets in the IED cannot be changed by th 06/21/2022 09:11 AM Actions
448 IEC 61850 User Feedback Task Force Feature 5 IOP_2013 Closed Normal ICD has a destination MAC address of 00:00:00:00:00. Is this valid for usage? 02/11/2021 07:50 AM Actions
412 IEC 61850 User Feedback Task Force Support 5 ENTSO-E Closed Normal There is a general issue that when we have signals connected to generic inputs, typically it is not possible to associate these 02/03/2021 02:54 PM Actions
577 IEC 61850 User Feedback Task Force Feature 49 ENTSO-E Closed Normal

IEC 61850-7-4

Switch on to Fault PSOF logical node 02/11/2021 06:02 AM Actions
576 IEC 61850 User Feedback Task Force Feature 48 ENTSO-E Closed Normal

IEC 61850-7-4

Distance protection: Distance protection - 1 phase and 3 phase zone extension signals are missing 12/06/2022 09:37 AM Actions
575 IEC 61850 User Feedback Task Force Feature 47 ENTSO-E Closed Normal

IEC 61850-7-4

Protection scheme: Reversal current logic LN/DO/DA missing 12/06/2022 09:36 AM Actions
574 IEC 61850 User Feedback Task Force Feature 46 ENTSO-E Closed Normal

IEC 61850-7-4

Protection scheme: Weak end infeed (1 phase and 2/3 phase operate missing) 12/06/2022 09:36 AM Actions
573 IEC 61850 User Feedback Task Force Feature 45 ENTSO-E Closed Normal

IEC 61850-7-4

Tap Changer Supervision: Tap discrepancy (3 pole transformer case) 12/06/2022 09:36 AM Actions
572 IEC 61850 User Feedback Task Force Support 44 ENTSO-E Resolved Normal

IEC 61850-7-500

S/S related applications: Auxiliary circuit supervision 05/09/2023 09:32 AM Actions
571 IEC 61850 User Feedback Task Force Support 43 ENTSO-E Closed Normal

IEC 61850-7-4

Insulation Supervision: Gas detector sensor 02/11/2021 06:54 AM Actions
570 IEC 61850 User Feedback Task Force Support 42 ENTSO-E Closed Normal

IEC 61850-7-5

Health: Health of prot relay/subfunction 02/11/2021 06:55 AM Actions
569 IEC 61850 User Feedback Task Force Support 41 ENTSO-E Closed Normal

IEC 61850-7-4

S/S related applications: Access security system 12/06/2022 09:36 AM Actions
485 IEC 61850 User Feedback Task Force Support 41 IOP_2013 Closed Normal Some switches discard the IEEE 802.1Q tag known as VLAN 0 on packets sent/received on the trunk ports. Others discard the packet 06/21/2022 09:00 AM Actions
484 IEC 61850 User Feedback Task Force Support 40 IOP_2013 Closed Normal A question was raised in regards can Report EntryIDs be reused after IED restart. If so, guidance needs to be given for system d 06/21/2022 09:00 AM Actions
568 IEC 61850 User Feedback Task Force Support 40 ENTSO-E Closed Normal

IEC 61850-90-3

S/S related applications: Fire detection/extinction 02/11/2021 06:59 AM Actions
411 IEC 61850 User Feedback Task Force Feature 4.3 ENTSO-E Closed Normal

IEC 61850-7-4, 7-3

Protection parameters not defined in P logical nodes 02/11/2021 06:08 AM Actions
410 IEC 61850 User Feedback Task Force Bug 4.2 ENTSO-E Closed High Data models using GGIO when not needed 02/09/2021 06:19 AM Actions
409 IEC 61850 User Feedback Task Force Feature 4.1 ENTSO-E Closed Normal Too loose or non existing guideline for organization of structure tree (construction of each LD, LN etc) 12/06/2022 09:00 AM Actions
441 IEC 61850 User Feedback Task Force Improvement 4 Vattenfall Closed High

IEC 61850-90-30

Limitations of one to one mapping between LNode and LN 12/05/2023 08:28 AM Actions
523 IEC 61850 User Feedback Task Force Support 4 IOP_2017/6 Closed Normal

IEC 61850-6

The R-GOOSE test area SCD was created by importing an ICD that was of schema 2007 B3. It exported 2007 B2 without removing/down 06/21/2022 09:16 AM Actions
489 IEC 61850 User Feedback Task Force Support 4 IOP_2015 Closed Normal

6

Declaration of Clients in an SCL file: The icd/iid file of a client only device can have a LN at the level of the access point. 06/21/2022 09:11 AM Actions
447 IEC 61850 User Feedback Task Force Feature 4 IOP_2013 Closed Normal

IEC 61850-6

Usage of IEDType - should it be mandatory? 02/11/2021 07:52 AM Actions
(1-50/3044) Per page: 25, 50, 100