What is the meaning of RptEna max=0?

Added by Herbert Falk over 3 years ago. Updated about 3 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Standard clarification required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
9
Source:
IOP_2013
TF Unique ID:
9 # IOP_2013
WG10 Proposal:

According to Cathedral City meeting (ref. to UFTF-CathedralMOM20160219) this issue is closed.

Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:

Clarify in the standard that RptEna max=0 is not a valid value.

Standard(s):

IEC 61850-6

Needs More Information:
Assigned TF:

Description

A question was raised about what is the meaning of RptEna max=0.
It was the discussion of the group that 0 should not be allowed if interpreted as having no instances of the RCB. In that case, the entire RCB should be missing from the SCL file.

#1

Updated by Vladan Cvejic about 3 years ago

  • Subject changed from A question was raised about what is the meaning of RptEna max=0. It was the discussion of the group that 0 should not be allowed to What is the meaning of RptEna max=0?
  • Status changed from New to Closed
  • Discuss in Upcoming Meeting set to No

Checking done.

#2

Updated by Vladan Cvejic about 3 years ago

  • Standard(s) set to IEC 61850-6