Feature #577
Switch on to Fault PSOF logical node
Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Standard extension required
Start date:
Due date:
% Done:
0%
Estimated time:
ID:
49
Source:
ENTSO-E
TF Unique ID:
49 # ENTSO-E
WG10 Proposal:
No issue. The Op DO is always ACT. Str DO is ACD. The direction information can be retrieved from Str DO.
Estimated Completion:
2019-06
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:
To revise PSOF LN
Standard(s):
IEC 61850-7-4
Needs More Information:
Assigned TF:
Description
Switch on to Fault: operate by SOTF (FW) and SOTF (BW)
PSOF LN is related to Switch onto fault and there is Str (ACD) where, for example, logic:
PSOF.Str.dirGeneral == Forward / Backward
could create both Operate by SOTF and Operate by SOTF respectively.
Updated by Carlos Rodriguez del Castillo about 3 years ago
- Subject changed from Switch on to Fault: operate by SOTF (FW) and SOTF (BW) PSOF LN is related to Switch onto fault and there is Str (ACD) where, for to Switch on to Fault PSOF logical node
Updated by Vladan Cvejic about 3 years ago
- Description updated (diff)
- Standard(s) set to IEC 61850-7-4
- Discuss in Upcoming Meeting set to No
Checking done.