Switch on to Fault PSOF logical node

Added by Herbert Falk about 3 years ago. Updated about 3 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Standard extension required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
49
Source:
ENTSO-E
TF Unique ID:
49 # ENTSO-E
WG10 Proposal:

No issue. The Op DO is always ACT. Str DO is ACD. The direction information can be retrieved from Str DO.

Estimated Completion:
2019-06
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:

To revise PSOF LN

Standard(s):

IEC 61850-7-4

Needs More Information:
Assigned TF:

Description

Switch on to Fault: operate by SOTF (FW) and SOTF (BW)
PSOF LN is related to Switch onto fault and there is Str (ACD) where, for example, logic:
PSOF.Str.dirGeneral == Forward / Backward

could create both Operate by SOTF and Operate by SOTF respectively.

#1

Updated by Herbert Falk about 3 years ago

  • Status changed from New to Closed
#2

Updated by Carlos Rodriguez del Castillo about 3 years ago

  • Subject changed from Switch on to Fault: operate by SOTF (FW) and SOTF (BW) PSOF LN is related to Switch onto fault and there is Str (ACD) where, for to Switch on to Fault PSOF logical node
#3

Updated by Vladan Cvejic about 3 years ago

  • Description updated (diff)
  • Standard(s) set to IEC 61850-7-4