Feature #577
Switch on to Fault PSOF logical node
Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Standard extension required
Start date:
Due date:
% Done:
0%
Estimated time:
ID:
49
Source:
ENTSO-E
TF Unique ID:
49 # ENTSO-E
WG10 Proposal:
No issue. The Op DO is always ACT. Str DO is ACD. The direction information can be retrieved from Str DO.
Estimated Completion:
2019-06
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:
To revise PSOF LN
Standard(s):
IEC 61850-7-4
Needs More Information:
Assigned TF:
Description
Switch on to Fault: operate by SOTF (FW) and SOTF (BW)
PSOF LN is related to Switch onto fault and there is Str (ACD) where, for example, logic:
PSOF.Str.dirGeneral == Forward / Backward
could create both Operate by SOTF and Operate by SOTF respectively.