Feature #576
Distance protection: Distance protection - 1 phase and 3 phase zone extension signals are missing
0%
To revise PDIS and exend with additional signals (zone extension)(19-06-06) To create Use-case with different scenarios in order to clearly define scope of application (Vladan C)
IEC 61850-7-4
Description
Distance protection: Distance protection - 1 phase and 3 phase zone extension signal missing
The zone extension is activated by the status of the autorecloser and the status of the teleprotection: if the autorecloser is in service and the teleprotection is out of service we extend the Z1 from 80% of the line to 100% of the line in order to trip on all faults on the full line is base time.
Updated by Vladan Cvejic over 3 years ago
- Subject changed from Distance protection: Distance protection - 1 phase and 3 phase zone extension signal missing The zone extension is activated by to Distance protection: Distance protection - 1 phase and 3 phase zone extension signals are missing
- Short Proposal changed from To revise PDIS and exend with additional signals (zone extension) (19-06-06) To create Use-case with different scenarios in order to clearly define scope of application (Vladan C) to To revise PDIS and exend with additional signals (zone extension)(19-06-06) To create Use-case with different scenarios in order to clearly define scope of application (Vladan C)
- Standard(s) set to IEC 61850-7-4
- Discuss in Upcoming Meeting set to No
Checking done.
Updated by Vladan Cvejic almost 2 years ago
- Status changed from In Progress to Closed
- To discuss in WG10 set to No
- Needs More Information set to Yes
Since there is no representation from ENTSO-E anymore we can close these tickets for now. Additionally, we can eventually re-open if in the future similar needs are identified by other users.