# Project Tracker ID Source Status Priority Standard(s) Subject Updated
472 IEC 61850 User Feedback Task Force Support 28 IOP_2013 Closed Normal An ED.2 SCT would not import an ED.1 SCL file. This needs to be addressed with rules of transformation and the definition of a s 06/21/2022 09:00 AM Actions
437 IEC 61850 User Feedback Task Force Support 28 ENTSO-E Closed Normal

IEC 61850-6

SCL: Use of InRef and ExtRef not possible in many tools 02/11/2021 06:57 AM Actions
557 IEC 61850 User Feedback Task Force Feature 29 ENTSO-E Closed Normal

IEC 61850-7-4

Lockout functionality: how to model by different protection functions? 02/11/2021 06:05 AM Actions
514 IEC 61850 User Feedback Task Force Support 29 IOP_2015 Closed Normal Priority of error checking in controls – i.e. position-reached instead of Blocked-by-switching-hierarchy. The order of checks i 06/21/2022 09:12 AM Actions
473 IEC 61850 User Feedback Task Force Support 29 IOP_2013 Closed Normal An SCL file was provided that had a <Val> for an OctetString value. A question was raised as to the correct format for the value 06/21/2022 09:00 AM Actions
446 IEC 61850 User Feedback Task Force Bug 3 IOP_2013 Closed High

IEC 61850-6

The actual format required for an ClientLN (used for ReportControl Block reservation) is not specified fully or in an understand 02/11/2021 06:30 AM Actions
522 IEC 61850 User Feedback Task Force Feature 3 IOP_2017/5 Closed Normal

IEC 61850-6

SCD file has “originalSclVersion=2007” for all IED, including Ed1 devices 06/21/2022 09:24 AM Actions
488 IEC 61850 User Feedback Task Force Support 3 IOP_2015 Closed Normal

6

An ICD file has predefined ReportControlBlock. With the SCT we attached a dataset to one URCB. Afterwards we decide to de-config 06/21/2022 09:11 AM Actions
440 IEC 61850 User Feedback Task Force Support 3 Vattenfall Closed Normal The specified sigal has a utility process name independent of used protcol. E.g. "start of distance protection". Also link to a 06/21/2022 09:19 AM Actions
407 IEC 61850 User Feedback Task Force Feature 3.1 ENTSO-E Closed Normal "Vendor/User” and “Vendor/Vendor” Interoperability list 02/11/2021 06:17 AM Actions
408 IEC 61850 User Feedback Task Force Bug 3.2 ENTSO-E Closed High PICS, MICS and other statements documents are not formally defined 02/09/2021 06:20 AM Actions
558 IEC 61850 User Feedback Task Force Support 30 ENTSO-E Closed Normal

IEC 61850-7-4

Busbar protection (BBP): Diff/Kirchoff BBP 12/06/2022 09:02 AM Actions
474 IEC 61850 User Feedback Task Force Support 30 IOP_2013 Closed Normal Should all SCTs support a substation section and the ability to associate LNodes into that section. 06/21/2022 09:00 AM Actions
559 IEC 61850 User Feedback Task Force Support 31 ENTSO-E Closed Normal

IEC 61850-7-4

Busbar protection: ARC detection protection 12/06/2022 09:02 AM Actions
515 IEC 61850 User Feedback Task Force Support 31 IOP_2015 Closed Normal These test cases assume that a server will send a negative response to an operate to the same value. Some servers will accept th 06/21/2022 09:12 AM Actions
475 IEC 61850 User Feedback Task Force Support 31 IOP_2013 Closed Normal With the renaming of LNTypes, DOTypes, etc., there should be a specification as to the maximum size for these names. The XSD sho 06/21/2022 09:00 AM Actions
560 IEC 61850 User Feedback Task Force Support 32 ENTSO-E Closed Normal

IEC 61850-7-4

Busbar protection: Simplified logic 02/11/2021 07:02 AM Actions
516 IEC 61850 User Feedback Task Force Support 32 IOP_2015 Closed Normal Buffered reporting testing – anomaly with resynch (write of entryId failed, but buffered reports still sent). Because of indexe 06/21/2022 09:12 AM Actions
476 IEC 61850 User Feedback Task Force Support 32 IOP_2013 Closed Normal Currently, in SCL, the size of an array is numeric. This could lead to issues of consistency (e.g. one having 32 array elements 06/21/2022 09:00 AM Actions
561 IEC 61850 User Feedback Task Force Support 33 ENTSO-E Closed Normal

IEC 61850-7-500

Pole discrepancy: no LN to cover Trip and pole disc 02/11/2021 06:53 AM Actions
517 IEC 61850 User Feedback Task Force Support 33 IOP_2015 Closed Normal IEC 61850-9-3 slaves can by design lock themselves to IEEE C37.238 (Power Profile) masters. This is intended behavior, since IEC 06/21/2022 09:12 AM Actions
477 IEC 61850 User Feedback Task Force Support 33 IOP_2013 Closed Normal Throughout the IOP, there was discussion about validation. However, validation has several different levels to it. There is no v 06/21/2022 09:00 AM Actions
562 IEC 61850 User Feedback Task Force Support 34 ENTSO-E Closed Normal

IEC 61850-7-4

Transformer diff. protection: Restricted earthfault protection 02/11/2021 07:02 AM Actions
518 IEC 61850 User Feedback Task Force Support 34 IOP_2015 Closed Normal Does the SVID character have to be specifically mentioned to be within 10-34 characters? Some of the vendors have implemented th 06/21/2022 09:12 AM Actions
478 IEC 61850 User Feedback Task Force Support 34 IOP_2013 Closed Normal There is currently no mechanism to allow an array member to be added as a DataSet member In the conformance tables of 8-1, alter 06/21/2022 09:00 AM Actions
563 IEC 61850 User Feedback Task Force Support 35 ENTSO-E Closed Normal

IEC 61850-7-4

Transformer diff. protection: Protection blocked by harmonics 02/11/2021 07:01 AM Actions
479 IEC 61850 User Feedback Task Force Support 35 IOP_2013 Closed Normal An SCL file was produced that had a GOOSE DataSet that contained members that had FC=CO and FC=CF. The SCT performing the import 06/21/2022 09:00 AM Actions
564 IEC 61850 User Feedback Task Force Support 36 ENTSO-E Closed Normal

IEC 61850-90-6

S/S related applications: Auxiliary transfer 02/11/2021 07:01 AM Actions
480 IEC 61850 User Feedback Task Force Support 36 IOP_2013 Closed Normal A different client made use of a URCB that had been reserved in SCL for use by a different client via ClientLN. Currently, there 06/21/2022 09:00 AM Actions
565 IEC 61850 User Feedback Task Force Support 37 ENTSO-E Closed Normal

IEC 61850-7-4/90-3

S/S related applications: DC battery model and converter/charger/rectifier alarms 02/11/2021 07:00 AM Actions
481 IEC 61850 User Feedback Task Force Support 37 IOP_2013 Closed Normal A question was raised in regards to how a client should resynchronize to receive the last report (Buffered Reporting). The sta 06/21/2022 09:00 AM Actions
566 IEC 61850 User Feedback Task Force Support 38 ENTSO-E Closed Normal

IEC 61850-7-420

S/S related applications: Diesel aggregat alarm 12/06/2022 09:35 AM Actions
482 IEC 61850 User Feedback Task Force Support 38 IOP_2013 Closed Normal When should buffering start for a reserved and fully configured BRCB. The discussion was that buffering should probably begin up 06/21/2022 09:00 AM Actions
567 IEC 61850 User Feedback Task Force Support 39 ENTSO-E Closed Normal

IEC 61850-7-4

S/S related applications: 400VAC/110VDC 02/11/2021 07:00 AM Actions
483 IEC 61850 User Feedback Task Force Support 39 IOP_2013 Closed Normal A question was raised in regards to the expected behavior of a server/BRCB that has been purged (e.g. no events buffered) and th 06/21/2022 09:00 AM Actions
441 IEC 61850 User Feedback Task Force Improvement 4 Vattenfall Closed High

IEC 61850-90-30

Limitations of one to one mapping between LNode and LN 12/05/2023 08:28 AM Actions
523 IEC 61850 User Feedback Task Force Support 4 IOP_2017/6 Closed Normal

IEC 61850-6

The R-GOOSE test area SCD was created by importing an ICD that was of schema 2007 B3. It exported 2007 B2 without removing/down 06/21/2022 09:16 AM Actions
489 IEC 61850 User Feedback Task Force Support 4 IOP_2015 Closed Normal

6

Declaration of Clients in an SCL file: The icd/iid file of a client only device can have a LN at the level of the access point. 06/21/2022 09:11 AM Actions
447 IEC 61850 User Feedback Task Force Feature 4 IOP_2013 Closed Normal

IEC 61850-6

Usage of IEDType - should it be mandatory? 02/11/2021 07:52 AM Actions
409 IEC 61850 User Feedback Task Force Feature 4.1 ENTSO-E Closed Normal Too loose or non existing guideline for organization of structure tree (construction of each LD, LN etc) 12/06/2022 09:00 AM Actions
410 IEC 61850 User Feedback Task Force Bug 4.2 ENTSO-E Closed High Data models using GGIO when not needed 02/09/2021 06:19 AM Actions
411 IEC 61850 User Feedback Task Force Feature 4.3 ENTSO-E Closed Normal

IEC 61850-7-4, 7-3

Protection parameters not defined in P logical nodes 02/11/2021 06:08 AM Actions
568 IEC 61850 User Feedback Task Force Support 40 ENTSO-E Closed Normal

IEC 61850-90-3

S/S related applications: Fire detection/extinction 02/11/2021 06:59 AM Actions
484 IEC 61850 User Feedback Task Force Support 40 IOP_2013 Closed Normal A question was raised in regards can Report EntryIDs be reused after IED restart. If so, guidance needs to be given for system d 06/21/2022 09:00 AM Actions
569 IEC 61850 User Feedback Task Force Support 41 ENTSO-E Closed Normal

IEC 61850-7-4

S/S related applications: Access security system 12/06/2022 09:36 AM Actions
485 IEC 61850 User Feedback Task Force Support 41 IOP_2013 Closed Normal Some switches discard the IEEE 802.1Q tag known as VLAN 0 on packets sent/received on the trunk ports. Others discard the packet 06/21/2022 09:00 AM Actions
570 IEC 61850 User Feedback Task Force Support 42 ENTSO-E Closed Normal

IEC 61850-7-5

Health: Health of prot relay/subfunction 02/11/2021 06:55 AM Actions
571 IEC 61850 User Feedback Task Force Support 43 ENTSO-E Closed Normal

IEC 61850-7-4

Insulation Supervision: Gas detector sensor 02/11/2021 06:54 AM Actions
573 IEC 61850 User Feedback Task Force Feature 45 ENTSO-E Closed Normal

IEC 61850-7-4

Tap Changer Supervision: Tap discrepancy (3 pole transformer case) 12/06/2022 09:36 AM Actions
574 IEC 61850 User Feedback Task Force Feature 46 ENTSO-E Closed Normal

IEC 61850-7-4

Protection scheme: Weak end infeed (1 phase and 2/3 phase operate missing) 12/06/2022 09:36 AM Actions
(101-150/1448) Per page: 25, 50, 100