494 IEC 61850 User Feedback Task Force Support 9 IOP_2015 Closed Normal

6

DUSTIN: Issue 1: X/Y Coordinates Upon exchanging the SCD file between SCT tools, the drawing/visualization of the single line d 06/21/2022 09:12 AM Actions
493 IEC 61850 User Feedback Task Force Support 8 IOP_2015 Closed Normal

6

An icd/iid file is not required to include the “original SCL” element. Is it required to be added to the IED instance in the SCD 06/21/2022 09:12 AM Actions
492 IEC 61850 User Feedback Task Force Support 7 IOP_2015 Closed Normal

6

(a) If a device does not support configuration of the ctlModel for a specific DO – what is the correct way to declare this? • De 06/21/2022 09:12 AM Actions
491 IEC 61850 User Feedback Task Force Support 6 IOP_2015 Closed Normal

6

Declaration of CtlModel for controllable CDCs (a) If a device does not support configuration of the ctlModel for a specific DO – 06/21/2022 09:11 AM Actions
490 IEC 61850 User Feedback Task Force Support 5 IOP_2015 Closed Normal

6

In the service section, an IED can declare “modify dataset” to be FALSE. That means, datasets in the IED cannot be changed by th 06/21/2022 09:11 AM Actions
489 IEC 61850 User Feedback Task Force Support 4 IOP_2015 Closed Normal

6

Declaration of Clients in an SCL file: The icd/iid file of a client only device can have a LN at the level of the access point. 06/21/2022 09:11 AM Actions
488 IEC 61850 User Feedback Task Force Support 3 IOP_2015 Closed Normal

6

An ICD file has predefined ReportControlBlock. With the SCT we attached a dataset to one URCB. Afterwards we decide to de-config 06/21/2022 09:11 AM Actions
487 IEC 61850 User Feedback Task Force Support 2 IOP_2015 Closed Normal

6

In the service section, there is the new element “client services”. That element includes GOOSE (default FALSE). Is it required 06/21/2022 09:11 AM Actions
486 IEC 61850 User Feedback Task Force Support 1 IOP_2015 Closed Normal

7-1, 7-4

An ICT has required LGOS configuration coming from SCT to be able to subscribe GOOSE. Is it the way it should work? And is it re 06/21/2022 09:11 AM Actions
507 IEC 61850 User Feedback Task Force Support 22 IOP_2015 Closed Normal If the client reads a SCD file and loads then the data model (or vice versa ???) what data shall a client compare? confRef’s, da 06/21/2022 09:10 AM Actions
513 IEC 61850 User Feedback Task Force Support 28 IOP_2015 Closed Normal

90-4

HSR and PRP are redundancy protocols. In order to prevent a single point of failure, many people are considering 2 red boxes 06/21/2022 09:09 AM Actions
456 IEC 61850 User Feedback Task Force Support 13 IOP_2013 Closed Normal A client only ICD did not have a ClientServices section. An SCT imported the file and assigned used the IED to reserve a RCB wit 06/21/2022 09:00 AM Actions
485 IEC 61850 User Feedback Task Force Support 41 IOP_2013 Closed Normal Some switches discard the IEEE 802.1Q tag known as VLAN 0 on packets sent/received on the trunk ports. Others discard the packet 06/21/2022 09:00 AM Actions
484 IEC 61850 User Feedback Task Force Support 40 IOP_2013 Closed Normal A question was raised in regards can Report EntryIDs be reused after IED restart. If so, guidance needs to be given for system d 06/21/2022 09:00 AM Actions
483 IEC 61850 User Feedback Task Force Support 39 IOP_2013 Closed Normal A question was raised in regards to the expected behavior of a server/BRCB that has been purged (e.g. no events buffered) and th 06/21/2022 09:00 AM Actions
482 IEC 61850 User Feedback Task Force Support 38 IOP_2013 Closed Normal When should buffering start for a reserved and fully configured BRCB. The discussion was that buffering should probably begin up 06/21/2022 09:00 AM Actions
481 IEC 61850 User Feedback Task Force Support 37 IOP_2013 Closed Normal A question was raised in regards to how a client should resynchronize to receive the last report (Buffered Reporting). The sta 06/21/2022 09:00 AM Actions
480 IEC 61850 User Feedback Task Force Support 36 IOP_2013 Closed Normal A different client made use of a URCB that had been reserved in SCL for use by a different client via ClientLN. Currently, there 06/21/2022 09:00 AM Actions
479 IEC 61850 User Feedback Task Force Support 35 IOP_2013 Closed Normal An SCL file was produced that had a GOOSE DataSet that contained members that had FC=CO and FC=CF. The SCT performing the import 06/21/2022 09:00 AM Actions
478 IEC 61850 User Feedback Task Force Support 34 IOP_2013 Closed Normal There is currently no mechanism to allow an array member to be added as a DataSet member In the conformance tables of 8-1, alter 06/21/2022 09:00 AM Actions
477 IEC 61850 User Feedback Task Force Support 33 IOP_2013 Closed Normal Throughout the IOP, there was discussion about validation. However, validation has several different levels to it. There is no v 06/21/2022 09:00 AM Actions
476 IEC 61850 User Feedback Task Force Support 32 IOP_2013 Closed Normal Currently, in SCL, the size of an array is numeric. This could lead to issues of consistency (e.g. one having 32 array elements 06/21/2022 09:00 AM Actions
475 IEC 61850 User Feedback Task Force Support 31 IOP_2013 Closed Normal With the renaming of LNTypes, DOTypes, etc., there should be a specification as to the maximum size for these names. The XSD sho 06/21/2022 09:00 AM Actions
474 IEC 61850 User Feedback Task Force Support 30 IOP_2013 Closed Normal Should all SCTs support a substation section and the ability to associate LNodes into that section. 06/21/2022 09:00 AM Actions
473 IEC 61850 User Feedback Task Force Support 29 IOP_2013 Closed Normal An SCL file was provided that had a <Val> for an OctetString value. A question was raised as to the correct format for the value 06/21/2022 09:00 AM Actions
472 IEC 61850 User Feedback Task Force Support 28 IOP_2013 Closed Normal An ED.2 SCT would not import an ED.1 SCL file. This needs to be addressed with rules of transformation and the definition of a s 06/21/2022 09:00 AM Actions
471 IEC 61850 User Feedback Task Force Support 27 IOP_2013 Closed Normal How should an SCL file express the initial value of GOCB.Ena and SVCB.Ena. It would appear that the Control Block schema definit 06/21/2022 09:00 AM Actions
470 IEC 61850 User Feedback Task Force Support 26 IOP_2013 Closed Normal An ICT provides an IID/ICD file that defines 4 GOCBs. The SCT imports this file, creates an SCD which has only 1 GOCB. The ICT r 06/21/2022 09:00 AM Actions
469 IEC 61850 User Feedback Task Force Support 25 IOP_2013 Closed Normal The iedType attribute is optional within SCL. However, some SCL tools use this as part of validation. Lack of the attribute/valu 06/21/2022 09:00 AM Actions
468 IEC 61850 User Feedback Task Force Support 24 IOP_2013 Closed Normal The mechanism for defining a GI attribute in a ED.2 RCB does not validate and import into an ED.1 ICT. 06/21/2022 09:00 AM Actions
467 IEC 61850 User Feedback Task Force Support 23 IOP_2013 Closed Normal There are normative ENUM definitions for 7-4. (e.g. Mod) but there is no guidance in regards to naming rules (e.g. Modkind). 06/21/2022 09:00 AM Actions
466 IEC 61850 User Feedback Task Force Support 22 (2) IOP_2013 Closed Normal In a SCD there were LNodes in the substation section that were not associated to a specific IED/LN instance. The question was if 06/21/2022 09:00 AM Actions
465 IEC 61850 User Feedback Task Force Support 22 (1) IOP_2013 Closed Normal In a SCD there were LNodes in the substation section that were not associated to a specific IED/LN instance. In particular, an S 06/21/2022 09:00 AM Actions
464 IEC 61850 User Feedback Task Force Support 21 IOP_2013 Closed Normal There is an issue about differentiation between “fixed” /preconfigured DataSets and those that can be changed in a SCT. Some ICT 06/21/2022 09:00 AM Actions
462 IEC 61850 User Feedback Task Force Support 19 IOP_2013 Closed Normal The use of ExtRef to subscribe to a SV was questioned. There are several different mechanisms that could be used in 61850-6 to s 06/21/2022 09:00 AM Actions
460 IEC 61850 User Feedback Task Force Support 17 IOP_2013 Closed Normal The usage of ClientLN in RptEna is optional. What does this mean. 61850-6 made this option for backward compatibility with ED.1. 06/21/2022 09:00 AM Actions
418 IEC 61850 User Feedback Task Force Support 10.1 ENTSO-E Closed Normal

IEC 61850-6

DataSets for GOOSE messaging - modeling with: only DA, only DO or both? 02/11/2021 08:02 AM Actions
415 IEC 61850 User Feedback Task Force Support 7.1 ENTSO-E Closed Normal

IEC 61850-7-2

Standard is written in general opinion that Ethernet is fully capable to carry all its tasks 02/11/2021 08:01 AM Actions
416 IEC 61850 User Feedback Task Force Support 8 ENTSO-E Closed Normal

IEC 61850-6

Implementation and integration software of different manufacturers should have same mandatory tasks in order to be used as tools 02/11/2021 08:00 AM Actions
443 IEC 61850 User Feedback Task Force Feature 6 Vattenfall Closed Normal

IEC 61850-7-1

Requirement for guideline - generic interfacing logical nodes are used for outputs and inputs ( destroys the semantic meaning of signals) 02/11/2021 07:58 AM Actions
447 IEC 61850 User Feedback Task Force Feature 4 IOP_2013 Closed Normal

IEC 61850-6

Usage of IEDType - should it be mandatory? 02/11/2021 07:52 AM Actions
448 IEC 61850 User Feedback Task Force Feature 5 IOP_2013 Closed Normal ICD has a destination MAC address of 00:00:00:00:00. Is this valid for usage? 02/11/2021 07:50 AM Actions
452 IEC 61850 User Feedback Task Force Feature 9 IOP_2013 Closed Normal

IEC 61850-6

What is the meaning of RptEna max=0? 02/11/2021 07:48 AM Actions
455 IEC 61850 User Feedback Task Force Feature 12 IOP_2013 Closed Normal How does a SCT know the maximum number of instantiated RCBs allowed in an IED and what the allowed distribution per RCB? 02/11/2021 07:47 AM Actions
423 IEC 61850 User Feedback Task Force Support 14 ENTSO-E Closed Normal Conformance test for SICS. 02/11/2021 07:47 AM Actions
457 IEC 61850 User Feedback Task Force Feature 14 IOP_2013 Closed Normal

IEC 61850-6

A SCL file is created without maxAttributes attribute defined. What does it mean semantically it the attr. is missing? 02/11/2021 07:46 AM Actions
425 IEC 61850 User Feedback Task Force Support 16 ENTSO-E Closed Normal

IEC 61850-6

Restrictions in the configuration to be described in the ICD Service section 02/11/2021 07:44 AM Actions
426 IEC 61850 User Feedback Task Force Support 17 ENTSO-E Closed Normal

IEC 61850-6

SCT and ICD Service section handling 02/11/2021 07:43 AM Actions
427 IEC 61850 User Feedback Task Force Support 18 ENTSO-E Closed Normal Functional constrained data shall include all levels of a hierarchy 02/11/2021 07:41 AM Actions
428 IEC 61850 User Feedback Task Force Support 19 ENTSO-E Closed Normal

IEC 61850-6

If 11 # ENTSO-E is not supported, vendors shall describe in the PIXIT document what they support 02/11/2021 07:40 AM Actions