7029 Client Issues Resolved Normal cFtN3 step 2: SetFile has no Ed1 specific error code 10/29/2024 09:03 AM Actions
6991 Server Issues Resolved Normal sCnf75 not all devices have control objects 11/12/2024 08:08 AM Actions
6990 Server Issues In Progress Normal sSvp9 step 4 PTP class not 6/7 with/without holdover time? 11/12/2024 09:10 AM Actions
6989 Server Issues Resolved Normal sSvp14 for Backwards the max MSVID is 34 char not 32 10/29/2024 08:56 AM Actions
6988 Server Issues In Progress Normal sCtl16 in TP1.3 is in conflict with 7-4 Table B.1 11/12/2024 09:12 AM Actions
6905 Server Issues Resolved Normal sSBOes8 why is time validated for Cancel but not for the Operate 10/29/2024 08:55 AM Actions
6902 Client Issues Resolved Normal cLogN5 has no Ed1 specific error code 10/29/2024 08:51 AM Actions
6897 Server Issues Resolved Normal sCnf7, sCnf66 services can be defined on IED and AccessPoint when identical 11/12/2024 08:31 AM Actions
6896 Server Issues Resolved Normal sSrv17 remove FC=EX not applicable for SetDataValues 10/29/2024 08:46 AM Actions
6881 SCL Tooling Issues Resolved Normal tDfe6b the SCT is not allowed to create new bindings 10/29/2024 08:43 AM Actions
6817 Server Issues Resolved Normal sBr25 purge only when attribute value change 08/06/2024 08:20 AM Actions
6816 Client Issues Rejected Normal cBr31 is mandatory but for not applicable "small" client controllers 07/23/2024 08:51 AM Actions
6795 Server Issues Closed Normal sCnf29 all subnetworks used for 61850 shall have type 8-MMS 06/10/2024 09:25 AM Actions
6793 Client Issues Resolved Normal cCnf13 the ICT tool shall refuse the configuration 05/28/2024 09:04 AM Actions
6780 Server Issues Closed Normal sGos23 q=test shall be processes as invalid 06/11/2024 09:30 AM Actions
6777 Client Issues Resolved Normal SCD import and Tool Functionality test procedures 05/28/2024 08:05 AM Actions
6776 Client Issues Resolved Normal cSBOns4 requires different control value 05/28/2024 08:07 AM Actions
6728 Client Issues Resolved Normal cSg13 refers to PIXIT entry Sg5/Sg6 but not clarified in the expected result 05/28/2024 08:17 AM Actions
6727 Client Issues Resolved Normal cDsN1bc, cFtN2 have no non-Ed2 specific error code 04/02/2024 08:42 AM Actions
6710 Server Issues Closed Normal sSrv13 does not specify that the lower hierarchy Mod.stVal shall not change 06/10/2024 04:09 AM Actions
6688 Client Issues Resolved Normal cSrvN10 - Ed1 specific error codes do not exist for MMS GetNameList 04/02/2024 08:42 AM Actions
6685 GOOSE Performance Issues Resolved Normal Device need to be certified for Ed2.1 server first 06/11/2024 08:28 AM Actions
6655 Client Issues Resolved Normal cLogN5 is missing in table A4.2 and certificate template 01/09/2024 08:28 AM Actions
6654 Client Issues Resolved Normal Tracking numbering mismatch Ed2 <> Ed2.1 01/09/2024 08:27 AM Actions
6631 SCL Tooling Issues Resolved Normal tTf1 (mustUnderstand) for the ICT test needs clarification 01/09/2024 08:59 AM Actions