sCnf29 all subnetworks used for 61850 shall have type 8-MMS

Added by Richard Schimmel 6 months ago. Updated 5 months ago.

Status:
Closed
Priority:
Normal
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
6
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCnf29
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

Some devices have separate network interfaces for MMS, GOOSE and SMV, with unique types(!). All these subnetworks shall have the same type "8-MMS".

The current sCnf29 only requires "at least one" subnetwork has type 8-MMS. Such device would incorrectly pass the test

Proposal:
Verify that all IEC 61850 related SubNetwork type's have value "8-MMS" when type is present or type is absent

#1

Updated by IEC 61850 TPWG 6 months ago

  • Status changed from New to Resolved
  • Assignee set to Richard Schimmel

Accepted

#2

Updated by Richard Schimmel 5 months ago

  • Status changed from Resolved to Closed
  • Closed Reason Test Procedure Update added
  • Closed Reason deleted (--Not Set---)