Activity

10/18/2024

04:42 AM Server Issues #7028: There is no conformance procedure/block for TimeOperated Control
TimeActivedOperate is a conditional service in block 12a, 12b, 12c and 12d. The corresponding test cases are: sDOns4,... Richard Schimmel
04:35 AM Client Issues #7029 (New): cFtN3 step 2: SetFile has no Ed1 specific error code
Same as for cSrvN10 and cLogN5 the SetFile has no Ed1 specific error code.
I propose to remove cFtN3 step 2 (step 1...
Richard Schimmel

09/27/2024

03:40 AM Server Issues #6904 (In Progress): sCtl14 in TP1.3 does not reflect the Issue #6214 resolution
Indeed sCtl14 need to be improved. PIXIT Ct30 is only about operate time and is not relevant for expected result step... Richard Schimmel

09/20/2024

07:04 AM Server Issues #6991 (New): sCnf75 not all devices have control objects
Change to conditional with condition:
Condition: when Operate is supported (PICS)
Richard Schimmel
06:55 AM Server Issues #6990 (New): sSvp9 step 4 PTP class not 6/7 with/without holdover time?
IEEE 1588 defines clock class 6-7-52-187. When the master clock looses the GPS signal the master will continue. After... Richard Schimmel
06:29 AM Server Issues #6989 (New): sSvp14 for Backwards the max MSVID is 34 char not 32
9-2LE figure 4 shows SvID 10..34 chars. The maximum length is 34 chars! The test case states 32 chars as maximum leng... Richard Schimmel
06:10 AM Server Issues #6988 (New): sCtl16 in TP1.3 is in conflict with 7-4 Table B.1
Table B.1 is very clear that if XCBR/XSWI/Loc=T a command with orCat bay/station/remote is Not Allowed. But in sCtl1... Richard Schimmel

09/11/2024

10:19 AM Server Issues #6905 (New): sSBOes8 why is time validated for Cancel but not for the Operate
sSBOes8 compares the SelectWithValue-Operate and SelectWithValue-Cancel
For the Operate (step2) we change ctlVal, ...
Richard Schimmel
02:27 AM Client Issues #6902 (New): cLogN5 has no Ed1 specific error code
Same as for cSrvN10 also the cLogN5 QueryLogByTime/After has no Ed1 specific error code.
I propose to deprecate this...
Richard Schimmel

09/09/2024

04:30 AM Server Issues #5961: sCtl16 shall specify LocSta/MltLev to match with table B.1
We assume by default that the CSWI.Loc and Xxxx.Loc have the same value: both are True or False. In the second part ... Richard Schimmel