11/11/2024

09:53 AM Server Issues #6991: sCnf75 not all devices have control objects
Solution (changes in bold):
Verify for each (instance of) DOType/DA[name=ctlModel] whose associated EnumType conta...
Richard Schimmel
09:48 AM Server Issues #6988: sCtl16 in TP1.3 is in conflict with 7-4 Table B.1
Improved version attached. Richard Schimmel

10/30/2024

04:25 AM Server Issues #6897: sCnf7, sCnf66 services can be defined on IED and AccessPoint when identical
Solution attached Richard Schimmel

10/29/2024

07:30 AM Server Issues #6886: Tissue 1897 Data-change and data-update inclusion bitstring bits set in a report
sRp3/sBr3 already states in the expected result: "the reason code is *one* of the configured trigger options". This ... Richard Schimmel

10/18/2024

04:42 AM Server Issues #7028: There is no conformance procedure/block for TimeOperated Control
TimeActivedOperate is a conditional service in block 12a, 12b, 12c and 12d. The corresponding test cases are: sDOns4,... Richard Schimmel
04:35 AM Client Issues #7029 (Resolved): cFtN3 step 2: SetFile has no Ed1 specific error code
Same as for cSrvN10 and cLogN5 the SetFile has no Ed1 specific error code.
I propose to remove cFtN3 step 2 (step 1...
Richard Schimmel

09/27/2024

03:40 AM Server Issues #6904 (In Progress): sCtl14 in TP1.3 does not reflect the Issue #6214 resolution
Indeed sCtl14 need to be improved. PIXIT Ct30 is only about operate time and is not relevant for expected result step... Richard Schimmel

09/20/2024

07:04 AM Server Issues #6991 (Resolved): sCnf75 not all devices have control objects
Change to conditional with condition:
Condition: when Operate is supported (PICS)
Richard Schimmel
06:55 AM Server Issues #6990 (In Progress): sSvp9 step 4 PTP class not 6/7 with/without holdover time?
IEEE 1588 defines clock class 6-7-52-187. When the master clock looses the GPS signal the master will continue. After... Richard Schimmel
06:29 AM Server Issues #6989 (Resolved): sSvp14 for Backwards the max MSVID is 34 char not 32
9-2LE figure 4 shows SvID 10..34 chars. The maximum length is 34 chars! The test case states 32 chars as maximum leng... Richard Schimmel