Issues #7221
sGos22 should verify the extended quality, but the test procedure only mentions the value
Description
sGos22 verifies K2.17 rules extended packed list like the quality.
To verify the subscribe to the quality it need to be configured as such and also the simulator need to change the quality.
Proposal:
Expected result add 'and quality'
1. DUT sends GOOSE message or Report with state and quality change reflecting the extended DA state and quality change
2. DUT sends GOOSE message or Report with state and quality change reflecting the edition 2 state and quality change
3. DUT sends GOOSE message or Report with state and quality change reflecting the extended DA state and quality change
4. DUT sends GOOSE message or Report with state and quality change reflecting the edition 2 state and quality change
Test description add 'and quality'
1. Publisher changes the value and quality of the extended dataset element as FCD
2. Publisher changes the value and quality of the Ed2 dataset element as FCD
3. Publisher changes the value and quality of the extended dataset element as FCDA
4. Publisher changes the value and quality of the Ed2 dataset element as FCDA
Comment add '+q'
Configure DUT to subscribe to the normal Ed2 Ind1.ST.stVal +q and Ind2.ST.stVal +q as well as FutInd1.ST.stVal +q and FutInd2.ST.stVal +q
Updated by IEC 61850 TPWG 25 days ago
- Due date set to 06/10/2025
- Status changed from New to Resolved
- Assignee set to Richard Schimmel