IEC 61850 TPWG
- Login: IEC61850_TPWG
- Registered on: 07/26/2022
- Last connection: 12/03/2024
Issues
open | closed | Total | |
---|---|---|---|
Assigned issues | 0 | 0 | 0 |
Reported issues | 10 | 19 | 29 |
Projects
Project | Roles | Registered on |
---|---|---|
IEC 61850 TPWG | IEC61850_TPWG_MANAGER | 01/10/2023 |
General Testing Issues | Manager, IEC61850_TPWG_MANAGER | 08/09/2022 |
Test Procedure Issues | IEC61850_TPWG_DEVELOPER, IEC61850_TPWG_REPORTER | 01/10/2023 |
Client | IEC61850_TPWG_MANAGER, IEC61850_TPWG_DEVELOPER, IEC61850_TPWG_REPORTER | 07/26/2022 |
GOOSE Performance | IEC61850_TPWG_MANAGER, IEC61850_TPWG_DEVELOPER, IEC61850_TPWG_REPORTER | 07/26/2022 |
SCL Tooling | IEC61850_TPWG_MANAGER, IEC61850_TPWG_DEVELOPER, IEC61850_TPWG_REPORTER | 07/26/2022 |
Server | IEC61850_TPWG_MANAGER, IEC61850_TPWG_DEVELOPER, IEC61850_TPWG_REPORTER | 07/26/2022 |
Activity
01/07/2025
- 08:59 AM Server Issues #7082 (Rejected): sCnf121 requires to use lnNs for the 61869-9 extensions
- Case 2 is not allowed per 7-1 Figure J.8
- 08:50 AM Server Issues #7084 (Resolved): sTmP5 clarify the format of LTMS.TmsSrc = GMCID
- Accepted
- 08:44 AM Server Issues #7089 (In Progress): sMdl4, sMdl6 and sMdl15 not possible for SV only device
- #2 accepted
(Similar to GOOSE-only devices) - 08:41 AM Server Issues #7091 (In Progress): sSrv17 - New value should be different from the previous one and not from the SCL value. Test case will not work twice with SPG setpoints.
- 08:40 AM General Testing Issues Improvement #7062 (Resolved): Need to be able to test Virtual IEC 61850 Devices
- 08:25 AM SCL Tooling Issues #6617 (Resolved): tIieN1 - can a popup warning be considered as 'not allowed'
- Tissue will be raised against part 6 Ed2.2
- 08:14 AM Server Issues #6886: Tissue 1897 Data-change and data-update inclusion bitstring bits set in a report
- Waiting for TISSUE resolution.
BCR can have both dchg and dupd in some rare cases. - 08:11 AM Server Issues #6988 (Resolved): sCtl16 in TP1.3 is in conflict with 7-4 Table B.1
12/10/2024
- 08:26 AM Server Issues #6990 (Resolved): sSvp9 step 4 PTP class not 6/7 with/without holdover time?
- When clock class = 187 MU shall set smpSync = 1 (value 52 to be deprecated). No holdover applies as clock signal is ...