sCtl20 is stating the wrong AddCause

Added by Michael Haecker 2 days ago.

Status:
New
Priority:
Normal
Due date:
Discuss in Upcoming Meeting:
Yes
Clause Reference:
A4.12
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCtl20
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

sCtl20 (Parameters change after select)

The expected results request AddCause "Parameter-change-in-execution". This is not the appropriate AddCause, for its meaning is that a control action is blocked due to running parameter change.

Since Ed.2 there is a more appropriate AddCause "Inconsistent-parameters" for this test case.