Issues #7226
sCtl20 is stating the wrong AddCause
Due date:
07/08/2025 (Due in 17 days)
Discuss in Upcoming Meeting:
Yes
Clause Reference:
A4.12
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCtl20
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
sCtl20 (Parameters change after select)
The expected results request AddCause "Parameter-change-in-execution". This is not the appropriate AddCause, for its meaning is that a control action is blocked due to running parameter change.
Since Ed.2 there is a more appropriate AddCause "Inconsistent-parameters" for this test case.
Updated by IEC 61850 TPWG 11 days ago
- Due date set to 07/08/2025
- Status changed from New to Rejected