Project

General

Profile

Issues #7291

sLog8 step 5 and 13 single logentry with multiple values not supported

Added by Richard Schimmel 13 days ago. Updated 13 days ago.

Status:
New
Priority:
Normal
Assignee:
-
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
8-1 table 155
61850 Standard:
8-1
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

part 7-2 states number of entries in a single log is a local issue. part 8-1 states bufTm is not mapped (treated as bufTm=0) so every state change result in a separate logentry. Also part 8-1 table 155 states that EntryContent data contains only one listOfVariable with variableTag+valueSpecification.

Step 13 expects the server to support a single log entry with multiple values. This is not possible according to table 155.

I propose to remove step 13 "Client sends valid QueryLogAfter with RangeStartTime equal to that with multiple entry value and with entry equal to the non-first entry at that time"

#1

Updated by Richard Schimmel 13 days ago

  • Subject changed from sLog8 step 13 single logentry with multiple values not supported to sLog8 step 5 and 13 single logentry with multiple values not supported

Also step 5 need to be updated from:
5. EQUIPMENT SIMULATOR forces several data changes of one or more data set members in the data set including multiple values of entry identifiers with same timestamp
to:
5. EQUIPMENT SIMULATOR forces several data changes of one or more data set members in the data set

Also available in: Atom PDF