sCnf29 all subnetworks used for 61850 shall have type 8-MMS
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
6
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCnf29
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:
Description
Some devices have separate network interfaces for MMS, GOOSE and SMV, with unique types(!). All these subnetworks shall have the same type "8-MMS".
The current sCnf29 only requires "at least one" subnetwork has type 8-MMS. Such device would incorrectly pass the test
Proposal:
Verify that all IEC 61850 related SubNetwork type's have value "8-MMS" when type is present or type is absent