Issues #6897
sCnf7, sCnf66 services can be defined on IED and AccessPoint when identical
Due date:
11/12/2024 (44 days late)
Discuss in Upcoming Meeting:
No
Clause Reference:
Table 50
61850 Standard:
6
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCnf7, sCnf66
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
Part 6 - Table 50 defines exactly what Services - Elements - Attributes are allowed on IED level and AccessPoint level. It also indicates if the value shall be identical or may be different.
Proposal: Verify that Services at IED and AccessPoint level match the requirements as defined in IEC 61850-6 Table 50.
Files
Updated by Richard Schimmel 4 months ago
- Subject changed from sCnf7 services can be defined on IED and AccessPoint when indentical to sCnf7, sCnf66 services can be defined on IED and AccessPoint when identical
- Clause Reference set to Table 50
- Initial Test Document set to TP1.3
- Test Case ID set to sCnf7, sCnf66
- 61850 Standard 6 added
Propose to merge sCnf7 and sCnf66 into sCnf7.
Updated by IEC 61850 TPWG about 2 months ago
- Due date set to 11/12/2024
- Status changed from New to In Progress
- Assignee set to Richard Schimmel
Accepted. Richard to add proposal.
Updated by Richard Schimmel about 2 months ago
Solution attached