Project

General

Profile

Issues #6897

sCnf7, sCnf66 services can be defined on IED and AccessPoint when identical

Added by Richard Schimmel 23 days ago. Updated 22 days ago.

Status:
New
Priority:
Normal
Assignee:
-
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
Table 50
61850 Standard:
6
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCnf7, sCnf66
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

Part 6 - Table 50 defines exactly what Services - Elements - Attributes are allowed on IED level and AccessPoint level. It also indicates if the value shall be identical or may be different.

Proposal: Verify that Services at IED and AccessPoint level match the requirements as defined in IEC 61850-6 Table 50.

Also available in: Atom PDF