Issues #6793
cCnf13 the ICT tool shall refuse the configuration
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
cCnf13
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
The current cCnf13 states:
Check if the DUT interprets client references in control blocks of other IEDs to find the control block instances allocated to the IED, and data sent to this IED (SICS I29). It shall not be possible to select an RCB instance assigned to another client
Some ICT tools perform the checks/final validation later on. The test procedure shall be more flexible how/when checks are performed.
Proposal: change "It shall not be possible to select an RCB instance assigned to another client"
Into: The ICT shall refuse the configuration when the user wants to select or selected an RCB instance assigned to another client"
Updated by IEC 61850 TPWG 7 months ago
- Status changed from New to Resolved
- Assignee set to Richard Schimmel