Project

General

Profile

Issues #7089

sMdl4, sMdl6 and sMdl15 not possible for SV only device

Added by Richard Schimmel 8 days ago.

Status:
New
Priority:
Normal
Assignee:
-
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
9-2
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sMdl6, sMdl15, sMdl4
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

The mandatory sMdl4, sMdl6 and sMdl15 require an MMS server in the device under test. However for an SV only device no MMS server is available.

Two proposals:
1) the test is passed for an SV only device
2) change to conditional "when GetDataValues is supported"

No data to display