Description

Part 7-2 states that BRCB reconfiguration has the same effect as purging the buffer if the attribute value changes.

Some devices still do purge the buffer even if the attribute value does not change. This causes intop issue in the field.
Propose to extend the sBr25 test to verify that if the attribute value is not changed the buffer is not purged