Project

General

Profile

Issues #6817

sBr25 purge only when attribute value change

Added by Richard Schimmel 5 months ago. Updated 4 months ago.

Status:
Resolved
Priority:
Normal
Due date:
08/06/2024 (about 4 months late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
7-2
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sBr25
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

Part 7-2 states that BRCB reconfiguration has the same effect as purging the buffer if the attribute value changes.

Some devices still do purge the buffer even if the attribute value does not change. This causes intop issue in the field.
Propose to extend the sBr25 test to verify that if the attribute value is not changed the buffer is not purged


Files

Solution to redmine 6817 sBr25.docx Solution to redmine 6817 sBr25.docx 21.9 KB Richard Schimmel, 07/26/2024 07:12 AM
#1

Updated by IEC 61850 TPWG 4 months ago

  • Due date set to 08/06/2024
  • Status changed from New to In Progress
  • Assignee set to Richard Schimmel

Accepted.

#3

Updated by IEC 61850 TPWG 4 months ago

  • Status changed from In Progress to Resolved
  • Test Case ID set to sBr25
#4

Updated by IEC 61850 TPWG 4 months ago

  • Initial Test Document changed from TP1.2 to TP1.3

Also available in: Atom PDF