Issues #6905
sSBOes8 why is time validated for Cancel but not for the Operate
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
7-2
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
sSBOes8 compares the SelectWithValue-Operate and SelectWithValue-Cancel
For the Operate (step2) we change ctlVal, origin, ctlNum, test and Check (not the TimeStamp!!)
But for the Cancel (step 6) we check the T time+1/-1min and expect "inconsistent parameter.
Proposal: remove T time+1/-1min check at step 6 Cancel.
Updated by IEC 61850 TPWG about 2 months ago
- Status changed from New to Resolved
- Assignee set to Richard Schimmel
Accepted.