Project

General

Profile

Issues #7082

sCnf121 requires to use lnNs for the 61869-9 extensions

Added by Richard Schimmel 2 months ago. Updated about 1 month ago.

Status:
Rejected
Priority:
Normal
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
7-1
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCnf121, sCnf122, sCnf123
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

According to the extension rules in part 7-1 we have 2 solutions to indicate a LN contains extension data objects:
1) the LN has lnNs=IEC61869-9
2) the extended data objects have dataNs=IEC61869-9

sCnf121, sCnf122, sCnf123 do require method 1). These test procedures should also allow method 2)

Proposal:
replace " The effective logical node namespace: lnNs = IEC 61869-9:2016[A] "
by " The logical node has lnNs=IEC61869-9:2016[A] and/or the extension Data Objects have dataNs=IEC61869-9:2016[A]"

#1

Updated by IEC 61850 TPWG about 1 month ago

  • Status changed from New to Rejected
  • Assignee set to Richard Schimmel

Case 2 is not allowed per 7-1 Figure J.8

Also available in: Atom PDF