Project

General

Profile

Issues #6988

sCtl16 in TP1.3 is in conflict with 7-4 Table B.1

Added by Richard Schimmel 7 days ago.

Status:
New
Priority:
Normal
Assignee:
-
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
Part 7-4 Table B.1
61850 Standard:
7-4
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

Table B.1 is very clear that if XCBR/XSWI/Loc=T a command with orCat bay/station/remote is Not Allowed. But in sCtl16 and PIXIT Ct29 it is allowed. It seems we don't need PIXIT Ct29 because Table B.1 is very clear.

We need to rewrite sCtl16 to match Table B.1.
- the pre-condition for the first steps is XCBR/XSWI.Loc=F and CSWI.Loc is True.
- When XCBR/XSWI/Loc=T a command with orCat bay/station/remote is Not Allowed
- remove PIXIT entry CT29

No data to display

Also available in: Atom PDF